首页 | 官方网站   微博 | 高级检索  
     

硅胶-水吸附式冷风机组的设计及性能实验
引用本文:王红斌,彭佳杰,孙海权,潘权稳,王如竹,王海亮,徐兆宏.硅胶-水吸附式冷风机组的设计及性能实验[J].化工学报,2019,70(Z1):186-192.
作者姓名:王红斌  彭佳杰  孙海权  潘权稳  王如竹  王海亮  徐兆宏
作者单位:1. 山东师范大学历山学院,山东 潍坊 2625002. 上海交通大学制冷与低温工程研究所,上海 200240
摘    要:吸附式冷风机组无须冷水回路和冷水泵,可满足小型化的应用需求。针对一种由2个吸附床,1个冷凝器和1个热管型的蒸发器的硅胶-水吸附式冷风机进行了实验研究,确定了机组的动态运行特性,探讨了热源温度、冷却水进口温度和冷风出口温度对系统性能的影响。实验结果表明,机组能够有效利用60~90℃范围内的低温热源,可提供0.84~2.29 kW的制冷量,系统的COP在0.26~0.43之间。

关 键 词:吸附  硅胶-水  冷风机  设计  解吸  
收稿时间:2018-10-17
修稿时间:2019-01-23

Design and experimental study on silica gel-water adsorption air cooler
Hongbin WANG,Jiajie PENG,Haiquan SUN,Quanwen PAN,Ruzhu WANG,Hailiang WANG,Zhaohong XU.Design and experimental study on silica gel-water adsorption air cooler[J].Journal of Chemical Industry and Engineering(China),2019,70(Z1):186-192.
Authors:Hongbin WANG  Jiajie PENG  Haiquan SUN  Quanwen PAN  Ruzhu WANG  Hailiang WANG  Zhaohong XU
Affiliation:1. Shandong Normal University Lishan College, Weifang 262500, Shandong, China2. Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, Shanghai 200240, China
Abstract:The adsorption air cooler does not require the cooling water circuit and the cooling water pump, so it can meet the needs of miniaturized applications. In this paper, a silica gel-water adsorption air cooler was experimentally studied, which consists of two adsorbers, one condenser and one heat pipe type evaporator. The dynamic operating characteristics of the cooler were obtained. This paper discusses the influence of heat source temperature, cooling water inlet temperature and cold air outlet temperature on system performance. The experimental results show that the cooler can be effectively driven by low-grade heat source at 60—90℃. The cooling capacity of 0.84—2.29 kW and the corresponding COPs of 0.26—0.43 were achieved.
Keywords:adsorption  silica gel-water  air cooler  design  desorption  
点击此处可从《化工学报》浏览原始摘要信息