首页 | 本学科首页   官方微博 | 高级检索  
相似文献
 共查询到19条相似文献,搜索用时 234 毫秒
1.
为实现220kV及以上等级交联聚乙烯(cross linked polyethylene,XLPE)电缆绝缘料研发,须对其基础树脂和成品料主要性能做出完整评价,并对比其与进口材料的差异。该文阐述国产220kV电缆绝缘料配方体系和生产工艺设计原理。以进口同等级绝缘料作为对比,通过萃取进口材料交联剂获得可供测试的提纯树脂,对比测试国产与进口绝缘料基础树脂的大分子结构和流变性能;对比分析国产与进口绝缘料XLPE的交流电气性能、热氧老化性能和交联性能。结果表明:国产基础树脂在分子量及分布、支化度、化学成分及流变性能上均与进口同等级电缆料基础树脂相近;国产220kV XLPE绝缘材料在击穿强度上与进口材料持平,且相比原始基础树脂在击穿性能上有所提高,介电损耗性能上优于进口材料;国产XLPE热氧老化性能、交联度和交联反应效率上优于进口材料,抗预交联性能上与之持平,国产材料相对更优的抗氧化性能导致交联剂用量偏大,交联反应产气量相对较大,但达到饱和脱气所需时间基本一致。  相似文献   

2.
交联聚乙烯(crosslinked polyethylene,XLPE)高压直流电缆是直流电网的核心设备,将XLPE高压直流电缆绝缘料国产化具有重要意义。基于欧洲主流超净低密度聚乙烯(low density polyethylene,LDPE)与国内知名企业生产的2种超净聚乙烯,分别制备XLPE试样,并完成脱气处理。测量与评估3种XLPE试样的直流击穿电场强度、直流电导率、空间电荷特性等电气性能指标,综合评估交联材料电气性能。其中,一种国产交联聚乙烯材料的击穿场强与电导率性能指标接近于参考绝缘材料性能指标,其空间电荷性能指标优于参考绝缘材料性能指标,确定了XLPE高压直流电缆绝缘料国产化的可行性。  相似文献   

3.
高压交联聚乙烯电缆绝缘料的国产化研究   总被引:2,自引:0,他引:2  
简述我国高压交联聚乙烯(XLPE)绝缘电力电缆及其绝缘料的市场情况,以国产商品化中压XLPE电缆的绝缘料为基准,分析国内外高压XLPE电缆绝缘料及其制品的绝缘性能,介绍了新上化高分子材料有限公司高压XLPE电缆绝缘料国产化的研发过程。  相似文献   

4.
为了研究士160 kV高压直流交联聚乙烯电缆绝缘料切片在标准雷电冲击电压和标准操作冲击电压下的击穿场强随温度的变化特性,设计了一套温度控制系统,试验温度控制在30~70℃,并采用三参数威布尔分布模型对试样的击穿场强进行统计分析。结果表明:温度对XLPE雷电冲击电压下的击穿特性影响较小,其击穿场强值随温度变化较小;高于40℃时,温度对操作冲击电压下的击穿场强有较大影响,其击穿场强随温度升高明显降低。在两种冲击电压下,大部分试样在冲击电压上升沿发生击穿,表明试样的击穿场强对电压变化率更为敏感。通过对XLPE的击穿原理分析,进一步阐述了陷阱和空间电荷是XLPE聚合物击穿的主要原因。  相似文献   

5.
为促进国产交联聚乙烯绝缘料在高压直流电缆绝缘中的应用,根据实验数据推导出国产交联聚乙烯绝缘料的电导率方程,得到了电导率与温度和电场之间的关系;实验测得五种不同厚度薄试样的击穿场强,根据双参数威布尔分布推导出绝缘料的击穿场强与厚度的关系,得出厚度为26 mm下绝缘材料的击穿场强;根据TICW 7.2标准设计出320 kV高压直流电缆的结构,利用Comsol Multiphysics软件仿真得出电缆在不同负荷状态下的电场和温度场分布。仿真结果表明:当导体绝缘内温差大于5.3℃时,绝缘外部场强开始高于内部场强;当导体温度为70℃时,绝缘内部电场最大值为15.1 kV/mm,远低于材料的击穿场强。通过仿真分析,为成功设计320 kV高压直流电缆提供参考。  相似文献   

6.
采用直流电缆用交联聚乙烯(cross-linked polyethylene,XLPE)绝缘料,制备100、200、300、400mm 4个不同厚度的试样,经70℃、100Pa真空环境下不同时间(0、24和72h)的脱气处理后,通过其直流击穿场强和空间电荷特性检测和比对分析,研究脱气处理对直流电缆绝缘击穿场强的影响。研究表明,对于相同厚度试样,脱气处理能有效提高XLPE的击穿场强,并减少电极附近的异极性电荷积累和试样内交联副产物含量,且相对较厚试样的击穿场强的提高更明显。相同脱气时间下,试样厚度的增加导致交联副产物含量的增加、两极附近异极性电荷量增加、电场畸变的增加和击穿场强的降低。在不同脱气时间下,对直流击穿场强与厚度依据反幂规律进行拟合,由拟合结果可知随脱气时间增加,系数k逐渐增大,指数因子n逐渐减小。通过建立一种e指数函数关系以拟合脱气时间对于反幂规律中参数k与n的影响,为达到最佳的脱气效果提供参考。基于非本征击穿模型分析,脱气能减少XLPE中预先已有的缺陷和加压过程中产生的缺陷数量。交流副产物含量的降低能减少造成试样击穿的杂质缺陷和异极性电荷的积累,提高XLPE的击穿场强。合适的绝缘厚度和脱气时间选择可以在节省成本的同时,最大程度地提高直流电缆的绝缘性能。  相似文献   

7.
目前,320 kV交联聚乙烯(crosslinked polyethylene,XLPE)直流电缆是已投运的最高电压等级的柔性直流电缆。XLPE高压直流电缆是柔性直流输电系统的核心设备,将XLPE高压直流电缆绝缘基料国产化具有重要意义。该文测量与评估了多种国内知名厂家生产的绝缘基料的直流击穿电场强度、空间电荷特性与直流电导率,对比国外超净基料、绝缘材料(超净基料+2%交联剂)对应电性能指标,优选出了两种国产基料,确定了320kV XLPE直流电缆绝缘料用基料国产化的可行性。最后,详细研究了国产基料直流电导率参数,确定了适合于国产基料的电导率拟合函数。  相似文献   

8.
本文提出了一种电缆绝缘杂质含量微观性能的评价方法,可有效避免纯净度评估过程中人工显微观测主观因素的影响.基于宽频介电阻抗谱法,研究35 kV和110 kV电压等级的XLPE电缆绝缘样品在不同程度冷热循环试验条件下介质损耗因数随测试频率的变化规律,仿真计算冷热循环过程中XLPE基体与杂质缺陷的界面应力特性,分析XLPE电缆绝缘的宽频介质损耗宏观物理量参数与材料纯净度等微观性能的相关性.结果表明:35 kV的XLPE电缆绝缘经过-196~50℃下10次冷热循环处理后,0.1~1.0 Hz低频介质损耗因数增大1倍以上,而110 kV的XLPE绝缘试样介质损耗因数未发生明显变化.仿真分析表明,冷热循环过程中聚乙烯绝缘与微观杂质间产生界面应力,界面区机械应力疲劳导致缺陷扩大,加剧低频介质损耗因数增大.  相似文献   

9.
随着交联聚乙烯(XLPE)绝缘直流电缆电压等级的提高,对半导电屏蔽料的质量及可靠性的要求也越来越高。选用了2种国外高电压等级用直流半导电屏蔽料、一种国产较为优秀的半导电屏蔽料和国内XLPE直流电缆绝缘料作为试验材料,测试了3种屏蔽料的热、电性能,屏蔽与绝缘的复合性能,研究了3种屏蔽料对XLPE绝缘空间电荷的影响。通过对试验结果的综合分析,提出了炭黑填充量、炭黑粒径和基体树脂以及界面结合情况是影响半导电屏蔽料体积电阻率和空间电荷注入的关键因素。  相似文献   

10.
高压直流电缆运行中的温度梯度效应导致电缆外绝缘层场强严重畸变,降低了绝缘的电气强度和使用寿命。在聚乙烯纳米复合材料的基础上,添加适量的交联剂、抗氧剂等制备了新型高压直流交联聚乙烯料,对其力学性能和电性能进行测试,并将其与国外主流XLPE直流电缆绝缘料的空间电荷积聚与场强畸变特性进行对比分析。结果表明:新型高压直流交联聚乙烯电缆料的性能优于国外主流XLPE直流电缆绝缘料,有望用于国产高压直流电缆。  相似文献   

11.
The use of nanocomposite polymers as electrical insulating materials has been growing rapidly in recent decades. The base polyethylene properties have been developed by adding small amounts of different fillers to the polyethylene material. It is economically to get polymer development by using cost-fewer nanoparticles; therefore, polyethylene dielectric properties are trapped by presence cost-fewer nanofillers like clay and fumed silica which are importance in development manufacture of power cables products. Dielectric strength is a vital pointer for quality of insulation materials of electrical power applications; hence, experimental measurements have been investigated on ac high voltage breakdown of new cost-fewer polyethylene nanocomposites materials. All experimental results of the new polyethylene nanocomposites have been compared with conventional polyethylene insulation materials; therefore, it has been specified the influence types and their concentrations of cost-fewer nanofillers on dielectric strength of polyethylene nanocomposite insulation materials.  相似文献   

12.
This paper reports the results from the condition assessment of 12- and 24-kV cross-linked polyethylene (XPLE) cables using a technique based on dielectric spectroscopy initially developed at KTH in Sweden. The work aims to examine whether the method could detect water tree degradation for the second generation medium voltage (MV) cables with long, but not bridging, water trees. While the overall cable condition was better than expected for second generation XPLE cables, water trees were found in most of the selected cables. The diagnostic method based on the measurement of the dielectric response could only detect water tree degradation in the examined second generation cables when the water trees bridged the insulation wall. Condition assessment above service stress may, in some cases, be required to detect bridging water trees. The results indicate that there is a correlation between the voltage level and the breakdown voltage of the cable. This can be used as a diagnostic criterion for this group of cables.  相似文献   

13.
The testing of oriented polyethylene tape with an embossed surface design for use as oil-impregnated insulation for flexible power cables is described. The development was carried out with small samples in the form of sheets, small cylindrical samples about 1 m long, and long cables either 15 m or 100 m long. Tests with these experimental configurations included investigating: (1) breakdown stress and statistics of breakdown; (2) dielectric loss measurements; (3) design of screens; (4) design of splices; (5) mechanical problems of taping and installing cables; and (6) oil impregnation and type of oil. The results point the way to the next development steps. These are: (1) development of thinner embossed tapes to exploit the potential of the high dielectric strength inherent in synthetic taped insulation; (2) development of accessories such as splices and terminations; and (3) complete system design to avoid a dramatic increase in dielectric loss caused by oil contamination. If the integrity of the insulation homogeneity can be maintained, it appears the high voltage breakdown stresses will be adequate to permit economical operation  相似文献   

14.
We measured the basic electrical insulation characteristic of biodegradable polylactic acid (PLA), and the following results were obtained. The volume resistivity, dielectric constant, and dielectric loss tangent measured at room temperature were almost the same as those of crosslinked polyethylene (XLPE) currently used as insulating material for cables and electric wires. The mean impulse breakdown strength of PLA was about 1.3 times that of XLPE. Also, space charge accumulation in PLA and XLPE was measured. The amount of space charge accumulation in PLA was one-half that in XLPE when a DC voltage was applied for a short time.  相似文献   

15.
为研究交联聚乙烯(cross-linked polyethylene,XLPE)绝缘材料的热分解活化能、电气特性和力学特性随热老化程度变化的规律,对交流电力电缆绝缘用XLPE材料在110 ℃下开展加速热老化实验。采用热失重(thermogravimtric analyzer, TGA)测试手段,对XLPE在20~600 ℃的热分解行为进行研究;采用交流击穿测试、宽频介电谱测试及体积电阻率测试,研究老化后XLPE试样的电气特性;采用拉伸实验测试,研究老化后XLPE试样的力学特性。结果表明:热老化使得XLPE的交联结构和结晶状态被破坏,XLPE活化能呈减小趋势。由于氧化反应快速进行,使得XLPE分子链发生断裂,交联结构变弱,导致XLPE绝缘材料严重劣化,其活化能、击穿强度、体积电阻率、弹性模量和断裂伸长率随老化时间增长呈下降趋势,而介电常数、介电损耗和电导率呈增加趋势。  相似文献   

16.
电缆附件在长期运行过程中,其界面硅脂与绝缘硅橡胶直接接触使其逐渐被硅橡胶吸收,导致硅橡胶性能下降,甚至引发电缆附件界面问题。文中以附件绝缘硅橡胶吸收硅脂的增重试验为基础,研究不同温度下硅脂/硅油在硅橡胶中的扩散规律并获得相应的扩散参数;研究硅脂对硅橡胶体积电阻率、相对介电常数、介质损耗角正切值和工频击穿场强等电气性能的影响规律。结果表明,不同温度下硅脂/硅油在硅橡胶中的扩散规律服从Langmuir扩散模型;硅橡胶对硅脂/硅油的吸收能力随温度升高而增强,且硅橡胶内硅油分子的脱附过程更强;随着硅橡胶对硅脂吸收量的增加,硅橡胶的体积电阻率逐渐降低,相对介电常数和介质损耗角正切值逐渐增加,但其工频击穿场强呈先增大后减小的趋势。  相似文献   

17.
为研究交联聚乙烯(cross-linked polyethylene,XLPE)绝缘材料的热分解活化能、电气特性和力学特性随热老化程度变化的规律,对交流电力电缆绝缘用XLPE材料在110 ℃下开展加速热老化实验。采用热失重(thermogravimtric analyzer, TGA)测试手段,对XLPE在20~600 ℃的热分解行为进行研究;采用交流击穿测试、宽频介电谱测试及体积电阻率测试,研究老化后XLPE试样的电气特性;采用拉伸实验测试,研究老化后XLPE试样的力学特性。结果表明:热老化使得XLPE的交联结构和结晶状态被破坏,XLPE活化能呈减小趋势。由于氧化反应快速进行,使得XLPE分子链发生断裂,交联结构变弱,导致XLPE绝缘材料严重劣化,其活化能、击穿强度、体积电阻率、弹性模量和断裂伸长率随老化时间增长呈下降趋势,而介电常数、介电损耗和电导率呈增加趋势。  相似文献   

18.
采用硅氧烷修复液修复交联聚乙烯电缆老化试样中的水树,进而分析修复效果及机理。将介质损耗因数为4%~6%,绝缘电阻7 500~10 000 MΩ的短电缆在7.5 kV 450 Hz交流电压下老化至介质损耗因数达到20%左右,绝缘电阻3 500~5 000 MΩ。然后用压力注入式修复装置把修复液注入缆芯对水树缺陷进行修复。以介质损耗因数、绝缘电阻和击穿电压为指标对修复效果进行评判;通过显微镜切片观察修复前后水树微观形态;通过仿真修复前后水树附近电场分布来分析和验证水树的修复机理。实验结果证明,修复液可以充分与电缆水树中的水发生反应生成胶状聚合物填充水树通道;修复后电缆介质损耗因数、绝缘电阻和击穿电压恢复到新电缆水平;改善了绝缘层电场分布;有效地抑制了水树生长。实验表明,该修复液可有效修复电缆中的水树缺陷,提高电缆绝缘水平。  相似文献   

19.
击穿强度通常是用来表征检测和使用过程中的绝缘材料状态和质量的指标之一。尽管有许多报道对聚乙烯(PE)和交联聚乙烯(XLPE)的击穿电压进行了研究,但是对热老化后的交联聚乙烯电缆的击穿行为的研究不是太多。表征威布尔统计分布参数,即范围和形状参数与分子结构、物理和化学缺陷的含量和形状以及其他的物理化学性能有密切的关系。本文的目的是研究不同热老化程度的XLPE电缆的威布尔统计分布参数的变化行为。研究结果显示威布尔参数变化对XLPE绝缘材料的热老化程度是非常敏感的,利用威布尔参数与热老化程度的关系可以有效地诊断PE和XLPE电缆绝缘材料。  相似文献   

设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号