共查询到20条相似文献,搜索用时 15 毫秒
1.
2.
3.
4.
反渗透水处理技术在富拉尔基发电厂锅炉补给水处理中的应用,与传统的离子交换除盐水处理系统的经济性进行对比,阐述了反渗透水处理技术的原理及应用优越性。 相似文献
5.
A. N. Samodurov S. E. Lysenko S. L. Gromov A. A. Panteleev E. B. Fedosseva 《Thermal Engineering》2006,53(6):439-443
The results of operation of DVS-M/150 installations for a total output of 150 m3/h (ZAO NPK Mediana-Fil’tr) at the Water Treatment Department of the Novocherkassk Thermal Power Plant (NchGRES) are presented, and the peculiarities of servicing reverse-osmotic systems under specific conditions of industrial power engineering are analyzed. In the range of high pH values, the disagreement between experimental and calculation data obtained by means of standard models is recognized. 相似文献
6.
V. I. Sharapov 《Thermal Engineering》2006,53(5):390-394
The results of industrial test investigations of an advanced spray-jet deaerator are discussed. The capability of attaining the specified quality of water at a flash-steam flowrate of 0.07 kg/t (that is, at an essential approximation to the theoretical specific flowrate) and the minimum residual oxygen content in the deaerated water is proved to be possible. 相似文献
7.
8.
9.
对进口反渗透设备在珠海发电厂水处理中应用的特点和影响因素进行较系统,详细的阐述,总结了实际运行管理应注意的问题。 相似文献
10.
11.
反渗透装置在水处理领域得到了应用,但其产水量和脱盐率两项基本性能参数的经常不达标造成装置运行故障,为解决这一问题通过对超临界机组反渗透装置运行参数水流量、水含盐量、系统压差等数据进行分析和现场调查,然后进行标准化计算,可以尽早、有效的发现反渗透系统运行过程中存在的问题。并及时的得到检修的处理。这种方法不仅简单,而且还能及进发现行过程中存在的问题,对于电厂的经济安全运行具有现实意义。 相似文献
12.
反渗透系统进水与浓水间压降增高是反渗透系统受到污染的症状之一.通过对郑州新力电力有限公司4套56m3/h反渗透系统频繁出现压降增高现象进行分析,找到了反渗透系统受污染的原因,采取有效的措施,保证了反渗透系统安全经济运行. 相似文献
13.
A. A. Panteleev B. E. Ryabchikov A. V. Zhadan O. V. Khoruzhii 《Thermal Engineering》2012,59(7):517-523
Two process circuits for demineralizing makeup water for power units at thermal power stations are considered. One of them is constructed on the basis of a combined plant comprising reverse-osmosis and ion-exchange apparatuses and the other comprises reverse-osmosis and electric deionization apparatuses. The considered circuits are analyzed by way of comparing them with the traditional chemical water demineralization system. Advantages and drawbacks of the new technologies for treating natural water are pointed out. 相似文献
14.
为了预防海水倒灌对电厂化学设备的影响,提出了以反渗透工艺降低进和除盐设备预脱盐水的含盐量的设想。从技术分析、经济比较和场地布置等方面进行探讨,得出该设想对于广州发电厂西村热电厂完全可行。 相似文献
15.
反渗透给水预处理系统故障分析及处理 总被引:1,自引:0,他引:1
反渗透给水的预处理一般包括源水到反渗透给水泵之前的一切处理.良好的预处理是反渗透装置长期稳定运行的必要条件.通过对郑州新力电力有限公司五期工程反渗透系统污染频繁、反渗透装置进石英砂等异常情况进行分析,提出相应的预处理系统改进方案,实施后,消除和减少了给水污染,为反渗透系统的可靠运行打下良好基础. 相似文献
16.
Gerard Bimont 《华东电力》2008,36(2):25-30
电厂远程监控和诊断是提高效率、降低成本、延长设备寿命、在行业竞争中保持优势的有效方法.结合法国燃煤电厂的实践,详细介绍了电厂电子监控系统的组成、功能和应用情况. 相似文献
17.
Hiroshi Enomoto Masashi Fujitsuka Tomoyasu Hasegawa Masatoshi Kuwada Akihiko Tanioka Mie Minagawa 《Electrical Engineering in Japan》2010,173(2):8-20
A pressure‐retarded osmosis (PRO) power generation system is a hydroelectric power system which utilizes permeation flow through a semipermeable membrane. Permeation flow is generated by the potential energy of the salinity difference between sea water and fresh water. Since the cost of the membrane is high, the permeation performance of the membrane must be improved in order to realize PRO systems. We have investigated reverse osmosis (RO) membrane products as semipermeable membranes and measured the permeation volume of a few products. The generation power per unit membrane area calculated from the permeation volume is about 0.62 W/m2. But as a result of our improvements (greater salt water volume, spacers for fresh water channel with the function of discharging concentrated salinity, extralow‐pressure type of membrane, washing the support layer of membrane when the generation power falls by half) the generated power may be 2.43 W/m2. Then the power system cost would be about 4.1 million yen/kW. In addition, if the support layer of the membrane is made thinner and a PRO system is applied to equipment where pumping power for another purpose is available (wastewater treatment plants located at the seaside, thermal and nuclear power plants, sea water desalination plants), the generated power may be increased. These improvements may enable PRO systems to be realized at a cost close to that of photovoltaic power systems. 2010 Wiley Periodicals, Inc. Electr Eng Jpn, 173(2): 8–20, 2010; Published online in Wiley InterScience ( www.interscience. wiley.com ). DOI 10.1002/eej.21000 相似文献
18.
论述反渗透系统由于设计上的不足、设备本身的缺陷,造成膜组件的损坏,在实际运行中发生的问题及针对存在的问题所采取解决方案。结果表明要确保反渗透的安全稳定运行,反渗透的前期过滤,药剂处理非常, 尤其要注意精密过滤器使用中滤芯两端的固定密封,精密过滤器更换滤芯后的冲洗及高压泵系统检验修后的肖理和高压冲洗,保障反渗透的安全稳定运行。 相似文献
19.
反渗透装置一段压差迅速上升的原因分析 总被引:1,自引:0,他引:1
针对大唐南京发电厂2×660MW超超临界机组化学水处理系统反渗透装置运行期间一段压差迅速上升问题进行了分析,故障原因为合有高分子助凝剂(聚丙烯酰胺)的污泥脱水分离液进入反渗透系统,造成反渗透膜严重污堵;采用了离线物理清理和在线化学清洗相结合的方法,使反渗透装置恢复了正常运行。分析结果走明:在化学水处理设置有反渗透系统的新建电厂中,合有高分子聚丙烯酰胺的污泥脱水分离液,应单独排放到工业废水池或煤冲洗水复用系统中,以免造成后续反渗透系统膜元件的严重污染。 相似文献
20.
反渗透处理苦咸水满足电厂用水技术指标 总被引:1,自引:0,他引:1
马乐农 《电力标准化与技术经济》2002,11(2):18-21
通过反渗透对沧州发电厂苦咸水的处理 ,对反渗透这种较新的水处理技术在我国的应用进行了介绍。沧州发电厂是我国第一套国产化反渗透装置的诞生地。 1 999年 ,为了向沧州大化供热 ,新建立了一个化学车间 ,系统设计容量 2 4 0t/h ,目前的出力 1 80t/h ,针对沧电地下水含盐量高的特点 ,系统采用反渗透预脱盐工艺。该系统自2 0 0 0年 1 2月正式投产以来 ,运行正常 ,反渗透脱盐率、回收率、后级离子交换系统的出水水质等技术指标都达到或超过国家规定的标准 相似文献