共查询到16条相似文献,搜索用时 109 毫秒
1.
2.
基于数学形态学的电力系统振荡中故障识别和改进的选相方法 总被引:11,自引:0,他引:11
为了使振荡闭锁装置能在振荡中再故障时开放保护,就必须能区分振荡与故障,且故障相的单相阻抗继电器在振荡时也应能正确测量阻抗。但如何在振荡中快速正确地选出一个故障相进行阻抗测量是距离保护能否有选择性地切除振荡中故障的关键问题。在动模实验中发现:对于振荡中发生的故障,在一定情况下序分量选相元件会误选相。文中利用级联多分辨形态梯度变换(SMMG)提出了一种电力系统振荡中的故障检测和改进的故障选相方案:先利用一个SMMG滤波器对相电流进行处理,构成一个自适应的振荡中故障起动元件;检测到故障或扰动后,对接地故障,如果由现有的序分量选相方法判断出其为落在包含单相和相间2种故障类型的区域,则可利用故障后3个模电流分量的SMMG系数局部模极大值确定其故障相别。用EMTP在一个系统模型上进行了大量的仿真研究,其结果验证了该方案的有效性和易用性,该方法判别灵敏,结果可靠,所提出的算法易于实现,在现有的微机保护装置中可以直接采用。 相似文献
3.
基于相间电阻变化特征的故障选相元件 总被引:1,自引:1,他引:0
针对现有选相元件在系统振荡期间存在误选相问题,提出了一种基于相间电阻变化特征的高压输电线路故障选相新原理。发生不对称接地故障时,首先利用零序和负序电流之间的相位关系分成3个区域,每个区域存在单相接地和两相短路接地2种故障类型,在判断出某个分区后根据相间测量电阻的变化特征得到选相结果。在系统振荡期间,健全相相间测量电阻是连续缓慢变化的;短路相之间的相间测量电阻,在发生故障瞬间是突变的,而故障后则基本没有变化。仿真结果表明,发生相间故障时,相间测量电阻不受负荷电流、过渡电阻、分支系数和系统振荡等的影响,该选相元件有很高的动作可靠性和准确性,适用于系统振荡期间的选相元件。 相似文献
4.
5.
一种新型振荡中故障选相元件 总被引:1,自引:0,他引:1
振荡中故障准确选相是有选择切除故障和确保距离保护正确动作的前提。在分析现有振荡中选相元件需开放条件配合,导致出口延迟,且易出现误选,进而导致距离保护误动的基础上,提出了一种新型选相元件,此元件首先利用零、负序故障分量进行故障分区,在分区的基础上改变目前采用阻抗确定故障相的做法,而采用Clark变换,分别通过α,β模量信息进行故障选相。此选相方法充分发挥了零、负序故障分量以及模量变化在振荡期间不涉及相量偏移带来计算误差等优势,有效避免了阻抗选相在振荡中的弊端。文中给出了基于RTDS动模仿真数据的测试结果,理论和测试表明:此方法在振荡期间能够可靠、快速、准确地区分故障类型。 相似文献
6.
同杆并架双回线阻抗选相方法研究 总被引:2,自引:0,他引:2
针对现有选相方法在同杆并架双回线跨线故障容易发生误选相的问题,提出了一种适用于同杆双回线的阻抗选相方法。新型选相方法主要利用了相间、单相阻抗大小及相位关系,为了实现在跨线故障、出口故障等情况下的准确选相,还补充了其它辅助判据以构成完整的选相方案。仿真计算表明,新的选相方法在同杆线路跨线故障、高阻接地、弱馈等故障情况下都有比较好的选相能力,适用于作为同杆并架线路保护故障选相元件。 相似文献
7.
8.
当前尚没有完全可靠的故障选相算法,误选相会导致阻抗测量模块不能得到与故障相对应的电流电压,从而产生很大的阻抗测量误差导致保护发生误动或拒动。基于110kV系统和以正序电压为极化量阻抗元件本身具有选相功能的特点,本文改变传统保护中先进行故障选相,后阻抗测量的思路,提出先阻抗测量,接着跳闸逻辑处理,最后再进行故障选相以形成故障报告的新方案。同时进行了最优化阻抗元件测量数量种类论证,给出了故障类型搜索算法流程和新方案的实现流程。试验结果表明该方案较好的解决了由于故障选相错误所导致的保护误动或拒动问题。 相似文献
9.
10.
基于同杆双回线跨线故障识别的选相方案 总被引:5,自引:1,他引:4
从同杆并架双回线跨线故障的特征出发,分析了现有主要选相元件在同杆并架线路发生跨线故障时存在的问题,提出了基于跨线故障识别的同杆双回线故障选相的新方案。系统发生故障后,选相元件首先根据故障后的零序电流、零序电压、正负序电流之间的关系等特征识别故障性质,针对双回线的跨线故障采用特殊的选相方案。可以有效地解决发生跨线故障时突变量选相元件和稳态选相元件存在的误动或者拒动的问题,提高了电力系统安全稳定运行和输电可靠性。 相似文献
11.
Li Zou Qingchun Zhao Xiangning Lin Pei Liu 《Power Delivery, IEEE Transactions on》2006,21(4):1847-1855
In order to prevent distance protection from tripping during power swing conditions, a power swing blocking device is often utilized. On the other hand, it has been an increasing requirement to achieve rapid clearance of internal faults during power swings. Accurate phase selection is a prerequisite to selective clearance of faults. An improved unbalanced fault phase selector during a power swing based on series multiresolution morphological gradient (SMMG) transform is proposed in this paper. As a feature extractor from raw signals, SMMG is employed to extract superimposed (fault component) current under the power swing condition in this paper. First, the operating characteristic of the sequence component fault phase selector during power swings is discussed. In order to overcome the disadvantage of the above selector, an improved fault phase selector for unbalanced faults during power swings is then proposed by using SMMG to extract superimposed components of modular current. The efficiency and feasibility of the proposed schemes are proven using a Power Systems Computer-Aided Engineering/Electromagnetic Transients including DC-based simulation on a sample power system. 相似文献
12.
基于相关分析和模糊推理的故障选相元件 总被引:4,自引:0,他引:4
提出了一种基于相关分析和模糊推理的故障选相元件。利用电流的故障分量提取出正、负、零序电流,然后对正、负序电流进行相关分析,利用模糊集合对相关系数建立多特征判据进行选相。该方案选相快速,不受过渡电阻、故障初始角的影响,与电流突变量差选相元件相比提高了在高阻接地时选相的灵敏度和两相接地短路时选相的可靠性。仿真结果验证了该选相方案的有效性。 相似文献
13.
基于相间故障弧光电压特征的高压线路选相元件 总被引:6,自引:0,他引:6
提出了一种基于相间故障弧光电压特征的高压线路选相新原理,应用于振荡闭锁期间的选相元件.对接地故障,利用零、负序电流相位差进行分区,每个分区包括某相单相接地和另外两相短路接地两种故障.然后根据相间故障弧光电压Ucosψ小于某一定值,而健全相相间电压的余弦值Ucosψ一般比较大的特征,来得到选相结果,解决了目前选相元件在电力系统振荡时可能发生的误选相问题.通过对不对称故障开放条件的改进,大大提高了单相接地故障的选相速度.该选相元件具有很强的耐过渡电阻能力,并且完全不受分支系数和系统运行方式的影响.RTDS试验验证了新选相元件的准确性和有效性. 相似文献
14.
15.
一种自动适应系统运行方式变化的新型突变量选相元件 总被引:1,自引:0,他引:1
针对传统电流突变量和电压突变量选相元件不能同时满足强弱电源系统侧保护要求的缺点,提出一种新的突变量选相原理。该选相元件在电压突变量基础上引入单相电流突变量进行极化,不但能自动适应系统运行方式的变化,尤其在系统正负序阻抗不等导致传统突变量选相元件失效的场合,更能体现出其优越性。值得指出的是,该选相元件对单相短路故障和相间短路(接地)判断均有很高的灵敏度。直流系统电磁暂态仿真结果表明,即使在正负序严重不对称的场合,该元件也具有很好的选择性。当系统参数大范围变化时,该选相判据也能实现正确选相,比传统突变量选相方案具有更高的可靠性。 相似文献