首页 | 本学科首页   官方微博 | 高级检索  
     


Performance characterisation of liquid desiccant columns for a hybrid air-conditioner
Authors:B. Shaji Mohan   M. Prakash Maiya  Shaligram Tiwari  
Affiliation:aRefrigeration and Air Conditioning Laboratory, Department of Mechanical Engineering, IIT Madras, Chennai 600036, India
Abstract:Use of liquid desiccant-vapor compression hybrid system is encouraged for low humidity applications. The liquid desiccant is primarily used to further dehumidify the supply air. In the present study, by using psychrometric equations and liquid desiccant property data, heat and mass transfer analysis for the dehumidifier and regenerator columns in counter flow configuration has been carried out. The simulation of the columns corresponds to low solution to air (S/A) flow ratio where precooled air gets dehumidified in the absorber while preheated air is used for regeneration of the solution. A detailed study of the performance characteristics for the absorber and regenerator columns confirms the requirement of the desiccant loop for additional dehumidification of the conditioned air. This need develops the main motive towards the concept of hybrid air conditioning.
Keywords:Liquid desiccant   Vapor compression   Hybrid system   Dehumidification   Regeneration
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号