首页 | 本学科首页   官方微博 | 高级检索  
     

金属辐射板与双冷源新风机组联合运行供暖特性试验研究
引用本文:宗天晴,傅允准. 金属辐射板与双冷源新风机组联合运行供暖特性试验研究[J]. 流体机械, 2022, 50(1): 16-21. DOI: 10.3969/j.issn.1005-0329.2022.01.003
作者姓名:宗天晴  傅允准
作者单位:上海工程技术大学,上海 201620
摘    要:
针对目前对双冷源新风机组与辐射板联合运行供暖系统应用于办公室的运行特性的研究很少的现状,搭建了金属辐射板与双冷源新风机组系统测试平台,测试了金属辐射板与双冷源新风机组空调系统供暖运行状态,以及双冷源新风机组供热性能、空气源热泵制热性能以及室内温度分布特性和室内空气品质.结果表明,金属辐射板与双冷源新风机组空调系统冬季供...

关 键 词:金属辐射板  双冷源新风机组  温度分布  室内空气品质  PM2.5

Experimental study on joint heating performance of double-cold-source fresh air unit and metal radiant panels
ZONG Tianqing,FU Yunzhun. Experimental study on joint heating performance of double-cold-source fresh air unit and metal radiant panels[J]. Fluid Machinery, 2022, 50(1): 16-21. DOI: 10.3969/j.issn.1005-0329.2022.01.003
Authors:ZONG Tianqing  FU Yunzhun
Affiliation:,Shanghai University of Engineering Science
Abstract:
In view of the current situation that few researches on the operational characteristics of dual-cold source fresh air dehumidifier and radiant panel combined refrigeration systems in the office were carried out,a test platform for metal radiant panel and dual-cold source fresh air dehumidifier was built,the heating operation status of the metal radiant panel and dual-cold source fresh air dehumidifier air-conditioning system was tested,and the heating performance of the dual-cold source fresh air dehumidifier and air source heat pump and indoor temperature distribution characteristics and indoor air quality were tested in detail.The results show that after 8 hours of operation of the metal radiant panel and dual-cold source fresh air dehumidifier air-conditioning system,the air temperature of the air outlet fluctuates at about 22 ℃,and the moisture content is 7 g/kg;While the indoor heat and humidity demand is achieved,the temperature distribution in vertical direction is uniform and the indoor temperature difference in vertical direction is 0.89 ℃/m;And the indoor air quality is good,concentration of CO_2 continuously dropsto 433 mg/L,and the concentration of indoor PM2.5 drops to 10 μg/m~3.The research results have a certain reference value for the in-depth study of the heating effect of the combined operation of the metal radiant panel and the dual-cold source fresh air dehumidifier and the engineering application of the system in areas hot in summer and cold in winter.
Keywords:metal radiant panel  dual-cold source fresh air dehumidifier  temperature distribution  indoor air quality  PM2.5
本文献已被 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏