首页 | 本学科首页   官方微博 | 高级检索  
     


Steam absorption process of water/LiBr system inside vertical small bore pipes
Authors:Masanori Kiyota  Itsuki Morioka  Daisuke Matsuura
Abstract:In a previous paper, a numerical model for absorption within vertical pipes was proposed and compared with the experiments. Agreements were good for pipes with an OD 28–15 mm but at 10 mm pipe experiments fell below the predicted values. For smaller diameters, the difference between the surface area of the falling liquid film and that of the outer surface of the pipe is not negligible and the thickness of the liquid film is also not negligible. In this paper a new model is formulated in cylindrical coordinates and experiments using pipes with 9.52 mm and 7 mm OD are done. Smooth pipes and two kinds of internally finned pipes, originally developed and used to enhance the heat transfer characteristics of the evaporator and condenser of a refrigerator using HFC as refrigerant, are tested in the experiments. The absorption performance is enhanced by 30% when compared to the smooth pipes, but the difference between the finned pipes is small. © 2004 Wiley Periodicals, Inc. Heat Trans Asian Res, 34(1): 18–28, 2005; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/htj.20040
Keywords:absorption refrigeration  heat transfer coefficient  mass transfer coefficient  mass absorption rate
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号