Nucleate boiling heat transfer coefficients of pure halogenated refrigerants |
| |
Authors: | Dongsoo Jung Youngil Kim Younghwan Ko Kilhong Song |
| |
Affiliation: | a Department of Mechanical Engineering, Inha University, Incheon 402-751, Republic of Korea;b Thermal/Flow Control Research Center, Korea Institute of Science and Technology, Seoul 130-650, Republic of Korea |
| |
Abstract: | Nuclate pool boiling heat transfer coefficients (HTCs) of HCFC123, CFC11, HCFC142b, HFC134a, CFC12, HCFC22, HFC125 and HFC32 on a horizontal smooth tube of 19.0 mm outside diameter have been measured. The experimental apparatus was specially designed to accomodate high vapor pressure refrigerants such as HFC32 and HFC125 with a sight glass. A cartridge heater was used to generate uniform heat flux on the tube. Data were taken in the order of decreasing heat flux from 80 to 10 kW m−2 with an interval of 10 kW m−2 in the pool of 7 °C. Test results showed that HTCs of HFC125 and HFC32 were 50–70% higher than those of HCFC22 while HTCs of HCFC123 and HFC134a were similar to those of CFC11 and CFC12 respectively. It was also found that nucleate boiling heat transfer correlations available in the literature were not good for certain alternative refrigerants such as HFC32 and HCFC142b. Hence, a new correlation was developed by a regression analysis taking into account the variation of the exponent to the heat flux term as a function of reduced pressure and some other properties. The new correlation showed a good agreement with all measured data including those of new refrigerants of significantly varying vapor pressures with a mean deviation of less than 7%. |
| |
Keywords: | Heat transfer Mass transfer Nucleate Boiling Refrigerant MeasurementAuthor Keywords: Transfert de chaleur Transfert de masse É bullition nuclé é e Frigorigè ne Mesure |
本文献已被 ScienceDirect 等数据库收录! |
|