The influence of a low viscosity oil on the pool boiling heat transfer of the refrigerant R507Influence d'une huile à faible viscosité sur le transfert de chaleur lors de l'ébullition libre du frigorigène R507 |
| |
Authors: | K Mohrlok K Spindler E Hahne |
| |
Abstract: | This paper describes the influence of a low viscosity polyolester based lubricating oil on the pool boiling heat transfer of the refrigerant R507. The pool boiling heat transfer coefficients for this refrigerant–oil mixture are measured on a smooth tube and on an enhanced tube. The investigation is made for oil mass fractions up to 10% and for saturation temperatures between −28.6°C and +20.1°C. For the smooth tube the heat transfer increases for increasing oil mass fractions up to 3% at lower saturation temperatures. At higher saturation temperatures the heat transfer decreases for increasing oil mass fractions for both tubes. For oil mass fractions greater than 1% at the higher saturation temperatures a range of decreasing heat transfer coefficient is found for increasing heat flux. The effect is caused by the different miscibility of the oil and the components of the refrigerant mixture. |
| |
Keywords: | Heat transfer Pool boiling Refrigerant R507 Polyolester Tube Heat transfer coefficient MeasurementAuthor Keywords: Transfert de chaleur Ebullition libre Frigorigè ne R507 Polyolester Tube Coefficient de transfert de chaleur Mesure |
本文献已被 ScienceDirect 等数据库收录! |