Performance analysis of air cycle refrigerator integrated desiccant system for cooling and dehumidifying warehouse
Authors:S.S. Elsayed   T. Miyazaki   Y. Hamamoto   A. Akisawa  T. Kashiwagi
Affiliation:aGraduate School of Bio-Applications and Systems Engineering, Tokyo University of Agriculture and Technology, Naka-cho 2-24-16, Koganei-shi, Tokyo 184-8588, Japan;bDepartment of Mechanical Engineering Science, Kyushu University, 6-10-1 Hakozaki, Higashi-Ku, Fukuoka 812-8581, Japan
Abstract:In this paper, the performance of air cycle refrigerator integrated desiccant system used to cool and dehumidify warehouse is analyzed theoretically. Simulation analysis is carried out to calculate the system coefficient of performance, cooling effects and the humidity change under different values of pressure ratio, storage zone temperature inside dock and outdoor air conditions. Also, the effect of the air cycle and the rotor parameters on the system performance is evaluated. From the simulation result it is found that, the desiccant system has the ability to supply air to the dock area at very low humidity. The system coefficient of performance increases due to the exhaust heat recovery on the desiccant system, and this enhancement can be more than 100%. The coefficient of performance of the proposed system is greater than that of a conventional system under the same operating conditions.
Keywords:Compression system   Modelling   Simulation   Thermodynamic cycle   Air   Cold store   Desiccant   Dehumidification   PerformanceMots clé  s: Systè  me à   compression   Modé  lisation   Simulation   Cycle thermodynamique   Air   Entrepô  t frigorifique    shydratateur    shumidification   Performance
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏