首页 | 本学科首页   官方微博 | 高级检索  
     


Condensation heat transfer coefficients of R22, R407C, and R410A on a horizontal plain, low fin, and turbo-C tubes
Authors:Dongsoo Jung   Chong-Bo Kim   Soo-Min Hwang  Kyung-Ki Kim
Affiliation:Department of Mechanical Engineering, Inha University, Inchon, 402-751, South Korea
Abstract:In this study, condensation heat transfer coefficients (HTCs) were measured on a horizontal plain tube, low fin tube, and Turbo-C tube at the saturated vapor temperature of 39 °C for R22, R407C, and R410A with the wall subcooling of 3–8 °C. R407C, a non-azeotropic refrigerant mixture, exhibited a quite different condensation phenomenon from those of R22 and R410A and its condensation HTCs were up to 50% lower than those of R22. For R407C, as the wall subcooling increased, condensation HTCs decreased on a plain tube while they increased on both low fin and turbo-C tubes. This was due to the lessening effect of the vapor diffusion film with a rapid increase in condensation rate on enhanced tubes. On the other hand, condensation HTCs of R410A, almost an azeotrope, were similar to those of R22. For all refrigerants tested, condensation HTCs of turbo-C tube were the highest among the tubes tested showing a 3–8 times increase as compared to those of a plain tube.
Keywords:Heat transfer   Mass transfer   Condensation   Tube   Enhanced tube   R22   R407C   R410A   Heat transfer coefficient   MeasurementAuthor Keywords: Transfert de chaleur   Transfert de masse   Condensation   Tube   Surface augmenté  e   R22   R407C   R410A   Coefficient de transfert de chaleur   Mesure
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号