首页 | 本学科首页   官方微博 | 高级检索  
     

热源位置对轴向槽道热管传热的影响
引用本文:栾涛,程林,曹洪振,曲燕.热源位置对轴向槽道热管传热的影响[J].化工学报,2007,58(4):848-853.
作者姓名:栾涛  程林  曹洪振  曲燕
作者单位:山东大学空间热科学研究中心
摘    要:探讨了轴向槽道热管垂直安装时热源位置的不同对热管工作特性的影响。当热源位于热管管内工质静止液面以下时,重力的作用提高了垂直安装热管的传热极限。热源相对于热管管内工质静止液面的位置不同时,热管的工作温度、启动过程以及传热极限都表现出不同的特性。当热源位于热管管内工质静止液面附近时,热管存在一个非正常启动过程,在该过程中热管的工作温度会发生瞬态的升高,然后逐渐恢复到正常的工作状态,该瞬态最高温度受热源位置、热管充液量、热管加热速率等因素的影响。当热源的位置高于热管管内工质静止液面一定距离后,热管将无法正常工作。

关 键 词:轴向槽道热管  热源位置  启动过程
文章编号:0438-1157(2007)04-0848-06
收稿时间:2006-3-31
修稿时间:2006-03-312006-05-11

Effects of heat sources on heat transfer of axially grooved heat pipe
LUAN Tao,CHENG Lin,CAO Hongzhen,QU Yan.Effects of heat sources on heat transfer of axially grooved heat pipe[J].Journal of Chemical Industry and Engineering(China),2007,58(4):848-853.
Authors:LUAN Tao  CHENG Lin  CAO Hongzhen  QU Yan
Affiliation:Center for Space Thermal Science, Shandong University, Jinan 250061, Shandong, China
Abstract:The effect of heat source location on the heat transfer of an axially grooved heat pipe was investigated. An abnormal startup process was observed when the heat source was located at a position on the heat pipe near the stationary level of the working liquid. The work temperature of the heat pipe showed a temporary increase during the abnormal startup process. The highest temperature in the abnormal startup process was influenced by the heat source location, heating rate and liquid volume in the heat pipe. When the heat source was located at different positions on the heat pipe below the stationary level of the working liquid, the working temperature, the startup process and the maximum heat load of the heat pipe were different. The heat pipe could not work normally, when the heat source was located on the heat pipe above the stationary level of the working liquid by a certain distance.
Keywords:axially grooved heat pipe  heat source position  startup process
本文献已被 CNKI 维普 万方数据 等数据库收录!
点击此处可从《化工学报》浏览原始摘要信息
点击此处可从《化工学报》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号