首页 | 本学科首页   官方微博 | 高级检索  
     


Performance of a solar-powered air conditioning system in Hong Kong
Authors:M.R. Yeung   P.K. Yuen   A. Dunn  L.S. Cornish
Abstract:To study the feasibility of utilizing solar power for comfort cooling in Hong Kong, a solar-powered absorption air-conditioning system was designed and successfully constructed on the campus of the University of Hong Kong (HKU). The system consisted of a flat-plate collector array with a surface area of 38.2 m2, a 4.7-kW nominal cooling capacity LiBr---H2O absorption chiller, a 2.75-m3 hot-water storage tank, a cooling tower, a fan-coil unit, an electrical auxiliary heater, a data-acquisition system and the associated control systems. In the present paper, the design of the HKU solar-powered air-conditioning system is described in detail and its performance over an entire cooling season is also discussed and compared with similar systems in Italy and Singapore. It was found that the HKU solar air-conditioning system had an annual system efficiency of 7.8% and an average solar fraction of 55%.
Keywords:
本文献已被 ScienceDirect 等数据库收录!