首页 | 本学科首页   官方微博 | 高级检索  
     


Impulse partial discharge and breakdown characteristics of rod–plane gaps in air and N2 gases
Authors:Hitoshi Saitoh  Keiichi Morita  Takashi Kikkawa  Naoki Hayakawa  Hitoshi Okubo
Abstract:In response to growing environmental concerns, we attempted to develop switchgear without using SF6 gas. In our research, we used compressed air and pure N2 as an electrical insulation gas, because of their low global warming potential. In this paper, we examined the impulse breakdown and impulse partial discharge characteristics under various conditions related to nonuniformity of the electric field. The experimental results show that the breakdown voltage (BDV) of air is higher than that of pure N2 gas under highly nonuniform field conditions in the rod–plane gap. On the other hand, the discharge inception voltage of air and N2 were almost the same. Furthermore, first partial discharge (PD), leader discharge, and its transition to the breakdown were successfully observed through the measurement of discharge current and light emissions under impulse voltage application. © 2004 Wiley Periodicals, Inc. Electr Eng Jpn, 148(3): 36–43, 2004; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/eej.10277
Keywords:air  N2  gas‐insulated switchgear  impulse partial discharge  breakdown characteristics