首页 | 本学科首页   官方微博 | 高级检索  
     

考虑一次调频死区的风储协同调频机理分析及死区参数优化
引用本文:李东东,陈治廷,徐 波,李沛泓,陈 浩.考虑一次调频死区的风储协同调频机理分析及死区参数优化[J].电力系统保护与控制,2024,52(4):38-46.
作者姓名:李东东  陈治廷  徐 波  李沛泓  陈 浩
作者单位:1.上海电力大学电气工程学院,上海 200090;2.国家电网有限公司华东分部,上海 200120
基金项目:国家自然科学基金项目资助(52377111)
摘    要:目前,调频死区对于风储联合调频的影响机理尚不明确,且风储最优调频死区参数难以获得。为此,对考虑一次调频死区的风储联合调频进行机理分析并提出最优的死区参数设置方案。首先,依据风电机组与电池储能的不同调频特性确定对应的死区模型,建立考虑风储一次调频死区的频率响应模型。其次,分析调频死区内外不同特征以及风储不同投入阶段对动态频率的影响,进而分段解析求解最大频率偏差时域表达式。然后,为兼顾调频效果与调频经济性,提出基于改进多目标粒子群(improved multi-objective particle swarm optimization, IMOPSO)算法的调频死区参数寻优方法。最后,仿真验证了将风储一次调频死区参数分别设置为0.0579 Hz和0.0386 Hz时所提方法的有效性。

关 键 词:调频死区  风储  联合调频  参数优化
收稿时间:2023/6/8 0:00:00
修稿时间:2023/8/14 0:00:00

Mechanism analysis and optimal dead zone parameter of wind-storage combined frequency regulation considering primary frequency regulation dead zone
LI Dongdong,CHEN Zhiting,XU Bo,LI Peihong,CHEN Hao.Mechanism analysis and optimal dead zone parameter of wind-storage combined frequency regulation considering primary frequency regulation dead zone[J].Power System Protection and Control,2024,52(4):38-46.
Authors:LI Dongdong  CHEN Zhiting  XU Bo  LI Peihong  CHEN Hao
Affiliation:1. College of Electric Power Engineering, Shanghai University of Electric Power, Shanghai 200090, China; 2. East China Branch, State Grid Corporation of China, Shanghai 200120, China
Abstract:At present, the influence mechanism of the frequency regulation dead zone on wind-storage joint frequency regulation is not clear. Also it is difficult to obtain the optimal frequency regulation dead zone parameters of the wind storage. Thus this paper analyzes the mechanism of wind-storage combined frequency regulation considering the dead zone of primary frequency regulation, and proposes an optimal dead zone parameter setting scheme. First, from the different frequency regulation characteristics of wind turbines and battery energy storage, a corresponding dead zone model is established, and a frequency response model considering the dead zone of primary frequency regulation of wind storage is established. Second, the influence of different characteristics inside and outside the frequency regulation dead zone and different input stages of wind storage on the dynamic frequency are analyzed, and then the time-domain expression of the maximum frequency deviation is determined segmentally. Then, to take into account both the effect and economy of frequency regulation, an optimization method of frequency regulation dead zone parameters based on the improved multi-objective particle swarm optimization (IMOPSO) algorithm is proposed. Finally, a simulation verifies the effectiveness of the proposed method when the dead zone parameters of primary frequency regulation of wind storage are set to 0.0579 Hz and 0.0386 Hz respectively.
Keywords:frequency regulation dead zone  wind-storage  combined frequency regulation  parameter optimization
点击此处可从《电力系统保护与控制》浏览原始摘要信息
点击此处可从《电力系统保护与控制》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号