基于DSP的高压容型电气设备介质损耗测量仪设计
引用本文:廖建庆.基于DSP的高压容型电气设备介质损耗测量仪设计[J].西北轻工业学院学报,2012(4):102-105,109.
作者姓名:廖建庆
作者单位:宁德师范学院物理与电气工程系
基金项目:宁德市科技计划项目(20110093);福建省教育厅科技项目(JB11193)
摘    要:针对电气设备易受电网频率波动和非整周期采样的影响,造成介质损耗因数tanδ测量精度和分辨率偏低的问题,提出一种基于DSP的高压电气设备介质损耗因数测量仪设计方案.将归一化工频电压信号和电流信号分别移相90°构成Hilbert变换对,再将两组复信号构造新的复三角信号模型实现对采样信号的去角频率处理.介绍了tanδ测量原理,给出了硬件各主要模块和系统软件实现方案.试验结果表明:该测量装置有效地解决了由于频率波动引起的非同步采样和非整周期截断问题,tanδ实际测量的绝对误差小于0.000 1,具有一定的实际推广价值.

关 键 词:介质损耗因数  Hilbert变换  移相  复三角函数  谐波干扰

Design of dielectric loss factor measurement with DSP for high voltage capacitive apparatus
LIAO Jian-qing.Design of dielectric loss factor measurement with DSP for high voltage capacitive apparatus[J].Journal of Northwest University of Light Industry,2012(4):102-105,109.
Authors:LIAO Jian-qing
Affiliation:LIAO Jian-qing(Department of Physics & Electrical Engineering,Ningde Normal University,Ningde 352100,China)
Abstract:Electrical equipment is vulnerable to fluctuations in the network frequency and non-integral period truncation conditions,and caused the dielectric loss factor measurement accuracy and resolution is low.An approach of dielectric loss factor measurement with DSP for high voltage capacitive apparatus is proposed.A Hilbert transform is build through moving voltage or current signals to 90 rad.The two signals are constructed a new complex triangle signal model.Introduced the dielectric loss factor measuring principle.The main modules and hardware system software scheme was given.Simulation and test results show that this algorithm reduced influence of non-synchronized sampling and non-integral period truncation caused by fluctuations in the network frequency.The absolute error of the dielectric loss factor is less than 0.000 1.It has practical application value.