摘    要:为了研究高海拔地区空气间隙的操作冲击特性,在大型人工气候室内对0.25~2m的棒-板间隙的操作冲击50%放电电压与气压p、间隙距离d的关系进行了系统的实验研究。结果表明:操作冲击50%放电电压U50随着气压p的下降呈幂指数关系下降,间隙长度不同,气压影响指数n不同;通过分析得到了不同间隙长度下的U50气压校正公式;U50与不同间隙距离d之间的关系与电压极性有关:正极性时U50与间隙距离d的线性关系较好,负极性时有明显的饱和性,且U50的气压影响特征指数n与电压极性有关。试验结果显示操作冲击50%放电击穿时间与电压极性和间隙距离有关。

关 键 词:操作冲击  棒-板间隙  低气压  放电特性  电压校正  间隙距离
文章编号:1003-6520(2007)11-0070-05
收稿时间:2006-04-01
修稿时间:2006-04-01

Switching Impulse Discharge Performance and Voltage Correction of Rod-Plane Air Gaps at Low Atmospheric Pressure
JIANG Xing-liang,YU Liang,YUAN Ji-he,HU Jian-lin,WANG Jun. Switching Impulse Discharge Performance and Voltage Correction of Rod-Plane Air Gaps at Low Atmospheric Pressure[J]. High Voltage Engineering, 2007, 33(11): 70-74
Authors:JIANG Xing-liang  YU Liang  YUAN Ji-he  HU Jian-lin  WANG Jun
Affiliation:1.The Key Laboratory of High Voltage Engineering and Electrical New Technology of Ministry of Education,Chongqing University,Chongqing 400044,China;2.Chongqing Power Grid Group,Yangjiaping Power Supply Bureau,Chongqing 400050,China;3.Tibet Electric Power Corp.,Lhasa 850000,China)
Abstract:The systemic switching impulse discharge tests of rod-plane air gaps with 0.25~2 m length were carried out in the large multi-function artificial climate chamber.The results show that the relationship between 50% switching impulse breakdown voltage U50 and the air pressure p is a power function,and the air pressure exponent n is influenced by the gaps length.The voltage correction formulas at low air pressure are gained by analyzing the experimental data.U50 is affected by voltage polarity,there is a nearly linear relation between the positive voltage and the gap length d while there is a nonlinear relation between the negative voltage and d.The exponent n is affected by voltage polarity also.The test results show that the voltage polarity and gap length have influences on the switching impulse breakdown time.
Keywords:switching impulse  rod-plane air gap  low air pressure  discharge performance  voltage correction  gap length