330kV变压器中性点两种接地方式比较
引用本文:邓秋荃,李琥,施围.330kV变压器中性点两种接地方式比较[J].西北水电,2003(1):39-41.
作者姓名:邓秋荃  李琥  施围
作者单位:西安交通大学,西安,710049
摘    要:研究330kV变压器中性点部分接地和经电抗器接地对中性点过电压和零序阻抗的影响。计算分析表明,330kV变压器中性点经适当数值的电抗接地较合理,推荐采用。

关 键 词:330kV变压器  中性点  接地电抗器  过电压  零序阻抗
文章编号:1006-2610(2003)01-0039-03
修稿时间:2002年10月28

Comparison of two grounding methods for 330 kV transformer neutral point
DENG Qiu-quan,LI Hu & SHI Wei.Comparison of two grounding methods for 330 kV transformer neutral point[J].Northwest Water Power,2003(1):39-41.
Authors:DENG Qiu-quan  LI Hu & SHI Wei
Abstract:The different effects on over - voltage of transformer neutral point and zero - sequence impedance by the neutral point grounding and the reactance grounding are discussed and compared. On the basis of analysis and calculation, the author puts forward it is rational to ground 330 kV transformers by appropriate reactance.
Keywords:transformer  neutral point  grounding reactance  over-voltage  zero -sequence impedance