首页 | 本学科首页   官方微博 | 高级检索  
     


Studying the Impulse Overloads in the Windings of a Station Service Voltage Transformer
Authors:A V Zhuikov  M A Kubatkin  D A Matveev  S I Khrenov  V S Larin  I I Nikulov
Affiliation:1.Moscow Power Engineering Institute,Moscow,Russia;2.All-Russian Electrotechnical Institute—branch of FSUE “RFNC-VNIITF”,Moscow,Russia;3.Ramensky Electrotechnical Plant “Energia”,Ramenskoe, Moscow oblast,Russia
Abstract:One of the key factors determining the performance of a 110–500-kV station service voltage transformer (SSVT) is a compact insulation design that provides minimum winding sizes. Since SSVTs are new equipment that combine the operational features of a power transformer and the design features of a measuring voltage transformer, it is necessary to study the characteristic transient processes occurring under the impact of lightning-impulse test voltages and lightning and switching overloads in operation in order to ensure proper insulation design. The article presents the results of an experimental investigation of impulse transients in the windings of a full-scale mockup model of an active part of a 20-kV A SSVT with a rated voltage of 110 kV. The influence of grounding the low-voltage winding terminals on the maximum values and duration of impulse stresses on the longitudinal insulation of the high-voltage winding is revealed. It is shown that, unlike in the case of power transformers with disc windings, more significant effects on the insulation are produced when no load is applied on the low-voltage windings.
Keywords:
本文献已被 SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号