Design of the winding–bushing interconnections in large power transformers
Authors:Z. Radakovic  E. Cardillo  M. Schaefer  K. Feser
Affiliation:(1) Siemens AG PTD T TI, Katzwanger Strasse 150, 90461 Nuernberg, Germany;(2) Institute of Power Transmission and High Voltage Technology (IEH), Pfaffenwaldring 47, 70569 Stuttgart-Vaihingen, Germany;(3) Siemens AG PTD T PN O, Katzwanger Strasse 150, 90461 Nuernberg, Germany
Abstract:
The paper presents the improvement in design of the conductor connecting the windings and bushings in oil power transformers. This is a sensitive part of large transformers and there is a need to optimise its manufacturing time and costs. The thermal problem of the heating of this conductor with increased insulation thickness on a part of it is treated using a non-linear two-dimensional thermal model. The experiments performed made determining of some problematic parameters (heat resistance of oil-paper insulation and the paper to oil convection heat transfer coefficient) of the thermal model feasible. The results obtained are of practical interest in the design practice of interconnections, but also affect the important parameters of heat transfer by devices with oil immersed paper insulation.
Keywords:Winding interconnection  Additional insulation  Temperature calculation