首页 | 本学科首页   官方微博 | 高级检索  
     

现场用GIS冲击耐压试验及局部放电检测装置设计
引用本文:孙强,董明,任重,任明,李彦明,邱爱慈.现场用GIS冲击耐压试验及局部放电检测装置设计[J].高电压技术,2012,38(3):639-644.
作者姓名:孙强  董明  任重  任明  李彦明  邱爱慈
作者单位:1. 国家电网西北规划评审中心,西安,710065
2. 西安交通大学电力设备电气绝缘国家重点实验室,西安,710049
3. 西安交通大学电力设备电气绝缘国家重点实验室,西安710049/西北核技术研究所,西安710024
摘    要:国内外一些研究和实际运行经验发现,已通过工频局部放电检测的不少GIS试品在投入运行后不久依然出现绝缘类故障,因此针对GIS设备提出进行冲击耐受试验及其局部放电检测,以及时发现内部隐患,确保设备安全稳定运行。在充分调研现场GIS冲击耐压试验及其局部放电检测必要性的基础上,结合GIS设备冲击耐受试验条件,设计了一套便于现场试验时的局部放电检测装置,利用该装置对800kV断路器和750kV变电站GIS组进行了冲击耐压试验下局放检测,并对现场检测的抗干扰措施进行了探讨。试验结果证明了GIS冲击电压下局部放电检测的可行性,及局部放电检测装置的有效性。

关 键 词:冲击电压  局部放电  GIS  SF6断路器  局部放电检测  现场试验技术

Field Test and Analysis of Partial Discharge on GIS Under Impulse Voltage
SUN Qiang,DONG Ming,REN Zhong,REN Ming,LI Yanming,QIU Aici.Field Test and Analysis of Partial Discharge on GIS Under Impulse Voltage[J].High Voltage Engineering,2012,38(3):639-644.
Authors:SUN Qiang  DONG Ming  REN Zhong  REN Ming  LI Yanming  QIU Aici
Affiliation:2,3(1.Northwest Programming and Reviewing Centre of State Grid,Xi’an 710065,China; 2.State Key Laboratory of Electrical Insulation and Power Equipment,Xi’an Jiaotong University, Xi’an 710049,China;3.Northwest Institute of Nuclear Technology of China,Xi’an 710024,China)
Abstract:It is shown that many GIS devices still have insulating faults even after they have passed partial discharge test under power frequency voltage.Hence,it is necessary to experimentally study the partial discharge on GIS under impulse voltage so as to timely identify internal incipient faults and to insure stable and safe operations of equipment.We designed a set of partial discharge detection devices which could be conveniently applied in the field experiment considering the conditions of impulse voltage experiment on the basis of investigating the necessity of partial discharge of GIS under impulse voltage,and applied the device in partial discharge detection on several 800 kV breakers and GIS devices of 750 kV substation.Moreover,we discussed anti-interference measures in field experiment.The results indicate that the test device is effective.
Keywords:impulse voltage  partial discharge  GIS  SF6 switchgear  PD detection  field test technology
本文献已被 CNKI 万方数据 等数据库收录!