首页 | 本学科首页   官方微博 | 高级检索  
     

肥西变电站220kV母线短路电流越限解决方案的研究
引用本文:叶斌,仇玉萍.肥西变电站220kV母线短路电流越限解决方案的研究[J].安徽电力,2007,24(3):13-16.
作者姓名:叶斌  仇玉萍
作者单位:安徽电网咨询有限公司,安徽电网咨询有限公司 安徽 合肥 230061,安徽 合肥 230061
摘    要:随着安徽电网规模的不断扩大,500 kV肥西变电站即将出现短路电流越限的问题,应及时研究其解决方案。比较电网解环、在变压器中性点加装小电抗及220 kV母线分裂运行等措施限制短路电流的效果,结合对电网的影响及适应性,推荐采取肥西变电站220 kV母线分裂运行的方案。

关 键 词:500  kV肥西变电站  220  kV母线  短路电流  电网解环  中性点小电抗  母线分裂运行  工频过电压
收稿时间:2007-08-06

Study of resolving scheme for short-circuit current exceeding limit of the 220 kV busbars of Feixi substation
Abstract:The capacity of Anhui Power Grid expands continuously, 500 kV Feixi station comes forth the question of short-circuit current exceeding limit, the resolving scheme should be studied in time. This paper presents grid disengaged loop, installing small reactors on neutral points of transformers and 220 kV husbars split operation , compares the impacts of restricting short-circuit current, combining the effects and flexibility of these schemes for power grid, the 220 kV busbars of Feixi substation spliting is recommended ultimately.
Keywords:500 kV Feixi transformer substation  200 kV husbar  short-circuit current  grid disengaged loop  small reactor on neutral point  split operation  power frequency overvoltage
本文献已被 CNKI 维普 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号