500 kV GIS及罐式断路器分合闸时间测试结果探讨 |
| |
引用本文: | 顾显华,曹阳,李凯.500 kV GIS及罐式断路器分合闸时间测试结果探讨[J].山东电力技术,2010(2):18-20,25. |
| |
作者姓名: | 顾显华 曹阳 李凯 |
| |
作者单位: | 山东电力超高压公司,山东济南250021 |
| |
摘 要: | 对于目前500 kV GIS及罐式双断口断路器分合闸时间测试方法只能得出一个断口时间结果的实际情况,指出并不能完全反映断路器整个机构的工作状态,并提出比较多次断路器分合闸时间的方法,通过历史数据的变化来考察断路器两个断口的实际工作状态。
|
关 键 词: | 500kV GIS 罐式断路器 双断口 机械特性 |
Discussion of Mechanical Characteristic Test of the Breaker of GIS and T-GCB of 500 Kilo-voltage |
| |
Abstract: | There is a situation that the close and open time test of the breaker of GIS and T-GCB of 500 kV that only one test result can be seen from double breaks.This article points that it can not reflect the whole working state of the,and gives a solution from comparison of many test results,which reviews the real operation of the two parts through the change of history data. |
| |
Keywords: | 500 kilo-voltage GIS T-GCB double-breaks mechanical characteristic |
本文献已被 CNKI 维普 等数据库收录! |
|