首页 | 本学科首页   官方微博 | 高级检索  
     

利用小波包能量区分变压器内外部故障
引用本文:李美蓉,公茂法,公政,张培杰,沈艳涛.利用小波包能量区分变压器内外部故障[J].电测与仪表,2015,52(16).
作者姓名:李美蓉  公茂法  公政  张培杰  沈艳涛
作者单位:山东科技大学 电气与自动化工程学院,山东科技大学 电气与自动化工程学院,山东电力集团公司潍坊供电公司,山东科技大学 电气与自动化工程学院,山东科技大学 电气与自动化工程学院
基金项目:国家级大学生创新创业训练计划资助项目(201210424046);山东省自然科学基金(ZR2012EEM021); 山东科技大学研究生科技创新基金(YC140338)
摘    要:TA饱和是变压器差动保护中待解决的关键问题之一。通过对变压器TA饱和的深入分析及仿真研究,得出结论:TA饱和时,区外故障电流含有大量明显的突变点,而区内故障电流连续。据此结论,文章提出了一种利用小波包变换区分变压器内外部故障的新方法。首先小波包变换分别对TA饱和情况下的内外部故障电流进行分解,然后对分解后的信号进行能量计算,将问题量化,可以直观地观察信号的差异,最后提出判据。仿真验证证明,该方法能够正确区分TA饱和情况下的内外部故障电流,能及时阻止可能造成的损害,并可防止变压器保护误动。

关 键 词:TA饱和  小波包能量  差动保护  变压器  误动作
收稿时间:2015/2/9 0:00:00
修稿时间:2015/4/12 0:00:00

Distinguish between Transformer Internal and External Fault Based on Wavelet Packet Energy
LI Meirong,GONG Maof,GONG Zheng,ZHANG Peijie and SHEN Yantao.Distinguish between Transformer Internal and External Fault Based on Wavelet Packet Energy[J].Electrical Measurement & Instrumentation,2015,52(16).
Authors:LI Meirong  GONG Maof  GONG Zheng  ZHANG Peijie and SHEN Yantao
Affiliation:College of Electrical Engineering and Automation,Shandong University of Science and Technology,College of Electrical Engineering and Automation,Shandong University of Science and Technology,Weifang Power Supply Company,Shandong Electric Power Corporation,College of Electrical Engineering and Automation,Shandong University of Science and Technology,College of Electrical Engineering and Automation,Shandong University of Science and Technology
Abstract:TA saturation is one of the key issues to be solved in transformer differential protection. Deep analysis and simulation study of transformer TA saturation showed that when TA saturate, external fault currents contain a great amount of point mutations, while the internal fault current continuous. According to the conclusion, we propose a new method for distinguishing transformer internal and external fault based on wavelet packet transform.First, wavelet packet transform respectively decompose internal and external fault current with TA saturation, then calculate energy of decomposed signals. The difference among signals is quantified and can be observed visually. Simulation results show that the method can distinguish internal and external fault current under the condition of TA saturation and timely prevent possible damage and can prevent transformer differential protection mal-operation.
Keywords:TA  saturation  Wavelet  packet energy  Differential  protection  Transformer  Mal-operation