500kV并联电抗器开断的过电压及限制措施
引用本文:邓雨荣. 500kV并联电抗器开断的过电压及限制措施[J]. 广西电力, 2000, 23(1): 15-17
作者姓名:邓雨荣
作者单位:广西电力试验研究院!广西南宁530023
摘    要:分析了500kV并联电抗器(以下简称高抗)开断的过电压的产生及影响,从断路器的并联电阻、避雷器及高抗的投切方式等几个方面探讨了过电压的限制措施及效果,并用试验进行验证。理论分析和试验表明,切除高抗会产生高达7倍的过电压。氧化锌避雷器是限制高抗开断的过电压的有效、经济措施,能将高抗开断的过电压限制在3倍以下;若再带上线路,在远方站间接切除高抗,其过电压可限制在2倍以下。采用这种方式,可安全、顺利地切除高抗。

关 键 词:并联电抗器  避雷器  限制  过电压
文章编号:1002-1361(2000)01-0015-03
修稿时间:1999-09-02

Switching On off Over voltage of 500 kV Shunt Reactor and its Restraint Measure
Deng YuRong. Switching On off Over voltage of 500 kV Shunt Reactor and its Restraint Measure[J]. Guangxi Electric Power, 2000, 23(1): 15-17
Authors:Deng YuRong
Abstract:The paper analyses the cause and effect of switching on off over voltage of 500 kV shunt reactor(called high voltage reactor thereinafter),and discusses the restraint measure of over voltage and its effect from several aspects,such as the shunt resistance of breaker,arrester and the switching on off manners of high voltage reactor,and checks them by test.The theoretical analysis and test have showed that switching off high voltage reactor may bring up to 7 times over voltage.The ZnO arrester is a sort of effective,economical equipment used to restraint the high voltage reactor's switching on off over voltage,and can restraint the switching on off over voltage under 3 times.If the line is also considered,and the high voltage reactor is cut off indirectly at remote station,its over voltage can be limited under 2 times.By this way,the high voltage reactor can be switched off safely and successfully.
Keywords:shunt reactor  arrester  restraint  over voltage  