电容式电压互感器分压电容介损现场测量时应注意的一个问题 |
| |
引用本文: | 刘滔,杨茂辉.电容式电压互感器分压电容介损现场测量时应注意的一个问题[J].电力电容器与无功补偿,2002(3). |
| |
作者姓名: | 刘滔 杨茂辉 |
| |
摘 要: | 分析了由于接触不良引起电容式电压互感器分压电容 C2 的介质损耗 tanδC2 偏大的测量误差及其消除方法
|
关 键 词: | 电容式电压互感器 接触不良 介质损耗 测量误差 |
A Problem to be Noticed for On-site Dielectric Loss Measurement of the CVT Voltage Dividing Capacitor |
| |
Abstract: | The error caused by loose contact in the dielectric loss factor (tanδ) measurement is analyzed. It is shown that loose contact will make the measured tanδof the voltage dividing capacitor C 2 in the CVT larger than it really is ,The method for eliminating this kind of error is proposed. |
| |
Keywords: | Capacitor voltage transformer(CVT) Loose contact Dielectric loss Measurement error |