首页 | 本学科首页   官方微博 | 高级检索  
     


Reduction of alternating current loss in a high-TC superconducting transmission cable by means of helical pitch adjustment
Authors:H Noji  S Ooyama  K Nakajima
Affiliation:Department of Electric Engineering, Miyakonojo National College of Technology, Miyakonojo 885-8567, Japan
Abstract:We have reported that the alternating current (ac) losses in a 66 kVrms 3-core high-TC superconducting (HTS) transmission cable fabricated by Tokyo Electric Power Company and Sumitomo Electric Industries Ltd. are calculated correctly by using an electric-circuit model. According to the calculated results, the circumferential field losses are dominant in the total ac losses in compared with the self-field losses and the axial-field losses. The helical pitches of each layer in the HTS cable are designed to obtain almost same layer currents, which gives the minimum self-field losses. We think that the optimum helical pitches giving the minimum total losses are different from the helical pitches designed by the companies and calculate the optimum values in the condition of the same helical direction of each layer in the cable. As a result, for example, it is found that the ac loss of 2.1 W m−1 cc−1 at transporting 1 kArms can be reduced to 1.8 W m−1 cc−1 (about 14% reductions) after redesigning the cable with the optimum helical pitches. The optimum helical pitches are obtained for each given transport current. After redesigning, the distribution of layer currents is not uniform and the circumferential fields are reduced.
Keywords:High-TC superconducting cable  Electric-circuit model  Alternating current loss
本文献已被 ScienceDirect 等数据库收录!