首页 | 本学科首页   官方微博 | 高级检索  
     


Thermography of aged contacts of high voltage equipment
Authors:M Muhr  S Pack  S Jaufer  H Lugschitz
Affiliation:Institut für Hochspannungstechnik und Systemmanagement, Technische Universit?t Graz, Graz, Austria
Verbund-Austrian Power Grid AG, Wien, Austria
Abstract:New developments in diagnostic tools and systems are necessary for a reliable and economic evaluation of the condition of equipment in power systems. In a research project a tool for the condition of contacts of centre break disconnector, which is used under normal operation by the aid of a thermography measurement system, has been developed. In this paper, an overview about the laboratory investigation of the temperature load behaviour and the environmental influence on-site for new and aged disconnector contacts are given. A condition evaluation tool for contacts, which was the aim of the project, has been created. The basic method for the evaluation is presented, and also two additional easements for a fast identification of suspect contacts are presented. With this evaluation tool and the usage of a thermography based measuring system, a condition based maintenance strategy can be applied, whereby an early detection of damages is possible and so power quality and reliability increase.
Keywords:High voltage disconnector  Contact diagnostic  Thermography  Aged contact
本文献已被 SpringerLink 等数据库收录!