Operation strategies of axial flow fans in a direct dry cooling system under various meteorological conditions
Authors:Wenhui Huang  Lei Chen  Lijun Yang  Xiaoze Du
Affiliation:Key Laboratory of Power Station Energy Transfer Conversion and System of Ministry of Education, School of Energy Power and Mechanical Engineering, North China Electric Power University, Beijing, China
Abstract:For a direct dry cooling system, the turbine back pressure fluctuates with the meteorological conditions. Moreover, the operation of axial flow fans plays an important role in the cooling performance of air-cooled condensers (ACC). It is of significant use to study the operation strategies of axial flow fans under various ambient conditions. Based on typical 2 × 660 MW direct dry cooling power generating units, the ACC model coupled with the turbine thermodynamic characteristics is developed, by which the thermo-flow performances of the ACC are predicted in the dominant wind direction, and then the standard coal consumption is calculated. The results show that the increased ambient temperature and wind speed, or the reduced fan rotational speed leads to the high turbine back pressure. At the low ambient temperature and wind speed, the standard coal consumption rate of the unit can be reduced by reducing the speed of axial flow fans appropriately, with the maximum drop in coal consumption rate reached 0.734 g/(kWh) when the ambient temperature is 10°C without wind. If the wind speed exceeds 12 m/s or the ambient temperature reaches 25°C, 110% of the rated fan rotational speed is recommended.
Keywords:air-cooled condenser  axial flow fan  direct dry cooling system  meteorological conditions  rotational speed  turbine back pressure
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号