首页 | 本学科首页   官方微博 | 高级检索  
     


Concentration measurement of refrigerant/refrigeration oil mixture by refractive index
Authors:Mitsuhiro Fukuta    Tadashi Yanagisawa    Satoshi Miyamura  Yasuhiro Ogi
Affiliation:Department of Mechanical Engineering, Shizuoka University, 3-5-1 Johoku, Hamamatsu, 432-8561, Japan
Abstract:Refrigeration oil having good miscibility with refrigerant is generally used in refrigeration units. Precise measurement of the mixing ratio of refrigerant to refrigeration oil is required for a sufficient understanding of the refrigeration cycle. In this paper, refractive index is chosen as a property which indicates the mixing concentration of the refrigerant/oil mixture. A laser displacement sensor is used to detect a change of optical path which changes according to the refractive index of test medium. The refractive indices of pure refrigerant, pure refrigeration oil and refrigerant/refrigeration oil mixture are measured with several combination of refrigerant/oil. It is found that the difference of refractive index between the refrigerant and the oil is sufficient for the measurement of the mixing concentration of refrigerant/oil mixture, and that the refractive index of the refrigerant/oil mixture changes almost linearly according to the mixing concentration. These data will be utilized for development of an in situ sensor in refrigerant compressors.
Keywords:
本文献已被 ScienceDirect 等数据库收录!