首页 | 本学科首页   官方微博 | 高级检索  
     


The role of measurement accuracy on the thermal environment assessment by means of PMV index
Authors:Francesca Romana d&rsquo  Ambrosio Alfano,Boris Igor Palella,Giuseppe Riccio
Affiliation:1. DIMEC - Dipartimento di Ingegneria Meccanica, Università di Salerno, Via Ponte Don Melillo, 84084 Fisciano (Salerno), Italy;2. DETEC - Dipartimento di Energetica, Termofluidodinamica Applicata e Condizionamenti Ambientali, Università degli Studi di Napoli Federico II, Piazzale Vincenzo Tecchio 80, 80125 Napoli, Italy
Abstract:ISO 7730 Standard classifies thermal environments in three categories as a function of the PMV range value, gradually decreasing according to the need of a lower dissatisfied percentage. It is noteworthy that the PMV value is greatly affected by the changes of its independent variables (air temperature, mean radiant temperature, air velocity, relative humidity, metabolic rate and clothing insulation); therefore the accuracy requirements of sensors for the measurement of environmental quantities as well the assessment of other parameters related to the activity and clothing appear a crucial matter. This work deals with a sensitivity analysis of PMV index to the accuracy of its six independent variables. Obtained results clearly show that the widths of PMV ranges fixed for each class in 7730 are near to the PMV uncertainty related to measuring devices accuracy, making often the environment classification a random operation.
Keywords:Thermal environment   Thermal comfort   Sensitivity analysis   PMV
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号