首页 | 本学科首页   官方微博 | 高级检索  
     

快速有选择性的辐射状配电网无通道保护
引用本文:陈飞,董新洲,薄志谦.快速有选择性的辐射状配电网无通道保护[J].电力系统自动化,2003,27(22):45-49.
作者姓名:陈飞  董新洲  薄志谦
作者单位:1. 清华大学电机系,北京市,100084
2. 阿尔斯通保护和控制公司,英国
基金项目:国家自然科学基金重点跟踪项目,国家自然科学基金资助项目 (5 0 0 770 1 1 ),国家自然科学基金国际合作基金资助项目(5 0 1 4 0 4 30 6 86 ),清华大学基础研究基金资助项目(JC2 0 0 0 0 2 1 )~~
摘    要:迄今为止的无通道保护只适用于双端电源线路。对于单电源配电线路,由于无电源侧的保护和断路器不会动作,该保护失去了动作依据。针对这个问题,文中提出了无电源侧的故障检测原理和基于该原理的无通道保护方案。使用新保护,当有电源或无电源一侧的断路器首先跳闸后,另一侧的继电器将根据检测到的网络变量加速本端动作,从而将故障线路从两端切除。对于一个典型的开环系统的仿真研究表明:所提出的无电源端的故障检测原理和保护方案是正确的;一个6段线路的系统最长保护动作时间不超过1.5s。

关 键 词:继电保护  辐射状配电网  继电器  无通道保护
收稿时间:1/1/1900 12:00:00 AM
修稿时间:1/1/1900 12:00:00 AM

FAST AND SELECTIVE NON-COMMUNICATION PROTECTION FOR RADIAL CONNECTED DISTRIBUTION SYSTEMS
Chen Fei ,Dong Xinzhou ,Z. Q. Bo.FAST AND SELECTIVE NON-COMMUNICATION PROTECTION FOR RADIAL CONNECTED DISTRIBUTION SYSTEMS[J].Automation of Electric Power Systems,2003,27(22):45-49.
Authors:Chen Fei  Dong Xinzhou  Z Q Bo
Affiliation:Chen Fei 1,Dong Xinzhou 1,Z. Q. Bo 2
Abstract:Up to now, the non communication protection is only suitable to the system with two sources. For the distribution line with only one source, the protection will lose the operation basis because the relay and the circuit breaker at the non source end will not work. To solve this problem, this paper presents a new technique to detect the fault from the non source side, and then a new non communication protection scheme is proposed based on the above technique. Within this scheme, when the circuit breaker at the source or non source side of the protected line opens firstly, the one at the other side will sense the change of the system and accelerate action in order to isolate the fault from the both ends of the line section. Extensive simulation studies with respect to a typical open ring system show that both the proposed fault detecting technique and the protection scheme are correct; the maximum operation time for a system with six sections is less than 1.5 s.
Keywords:relay protection  radial connected distribution network  relay  non  communication protection
本文献已被 CNKI 维普 万方数据 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏