XLPE电缆绝缘在线检测直流叠加法的接地
引用本文:王一,文习山,彭宁云,陈巧勇.XLPE电缆绝缘在线检测直流叠加法的接地[J].高电压技术,2003,29(7):34-36,51.
作者姓名:王一  文习山  彭宁云  陈巧勇
作者单位:武汉大学电气工程学院,武汉,430072
摘    要:运用直流叠加法的XLPE电缆在线检测装置投入6~35kV系统后,将使系统中PT中性点以及电缆屏蔽层的接线发生改变。通过基于ATP-EMTP软件的仿真计算以及相关分析,针对故障状态下发生PT饱和谐振时,改接线对6~35kV中性点不接地系统可能产生的影响作出分析并找出相应的解决办法。

关 键 词:XLPE电缆  在线检测  改接线影响  ATP-EMTP

Study on the Grounding in Superposing DC Current Method for the On-line Monitoring of XLPE Cable
Wang Yi et al.Study on the Grounding in Superposing DC Current Method for the On-line Monitoring of XLPE Cable[J].High Voltage Engineering,2003,29(7):34-36,51.
Authors:Wang Yi
Affiliation:Wang Yi et al
Abstract:If the XLPE cable on-line monitoring system, which is based on the method of superposing a low DC voltage on the neutral point of PT ,is used in 6-35 kV power system, the way of grounding of potential transformers and the shielding layer of cable must be changed. Depending on simulations with the ATP-EMTP and some correlative analysis, the paper analyzes the possible effects on power system caused by changes of the grounding way when there is a fault caused by the over saturated windings of a potential transformer, and gives corresponding methods to solve the problems.
Keywords:XLPE cable on line monitoring effects caused by change of grounding ways ATP-EMTP