首页 | 本学科首页   官方微博 | 高级检索  
     


Flow-boiling of R22, R134a, R507, R404A and R410A inside a smooth horizontal tube
Authors:A Greco  GP Vanoli
Affiliation:aFacoltà di Ingegneria, DETEC, Università degli Studi di Napoli Federico II, Pzle Tecchio 80, 80125 Napoli, Italy;bFacoltà di Ingegneria, Università del Sannio, Palazzo Bosco Lucarelli, Piazza Roma, Benevento, Italy
Abstract:Flow boiling heat transfer coefficients of R22, R134a, R507, R404A and R410A inside a smooth horizontal tube (6 mm I.D., 6 m length) were measured at a refrigerant mass flux of about 360 kg/m2 s varying the evaporating pressure within the range 3–12 bar, with heat fluxes within the range 11–21 kW/m2. The experimental data are discussed in terms of the heat transfer coefficients as a function of the vapour quality. The experimental results clearly show that the heat transfer coefficients of R134a are always higher than those pertaining to R22 (from a minimum of +6 to a maximum of +45%).
Keywords:Experiment  Boiling  Horizontal tube  R22  R134a  R507  R404A  R410A  Heat transfer coefficientMots clé  s: Experimentation  É  bullition  Tube horizontal  R22  R134a  R507  R404A  R410A  Coefficient de transfert de chaleur
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号