500kV双回换位塔电气模型设计优化的研究
引用本文:王茂成,刘晓辉,王孟勇,郝文婧.500kV双回换位塔电气模型设计优化的研究[J].电力建设,2006,27(12):21-23.
作者姓名:王茂成  刘晓辉  王孟勇  郝文婧
作者单位:1. 烟台电力设计院,山东省烟台市,264002
2. 山东电力集团公司,济南市,250001
3. 山东省鲁南地质工程勘察院,山东省兖州市,272100
摘    要:目前国内500kV双回换位塔的电气模型存在不利于复合绝缘子防上下伞裙的冰桥短接和防雷性能不足等缺点。通过安装侧针完善跳线防雷设计,改变跳线出口角度改善绝缘子高压端的场强分布,悬垂串和耐张串采用内弧结构的拉线型U形环避免芯棒与端部金具连接的扭伤,跳线串改成八字形或V字形以有效防污闪、雨闪和冰闪,耐张串采用复合绝缘子使双回换位塔完全免清扫。从而500 kV双回换位塔电气模型即可得到优化。

关 键 词:500kV双回线路  换位塔  电气模型  设计优化
文章编号:1000-7229(2006)12-0021-03
收稿时间:2006-09-11
修稿时间:2006年9月11日

Design Optimization Study of 500 kV Transposition Tower Electric Model
WANG Mao-cheng,LIU Xiao-hui,WANG Meng-yong,HAO Wen-jing.Design Optimization Study of 500 kV Transposition Tower Electric Model[J].Electric Power Construction,2006,27(12):21-23.
Authors:WANG Mao-cheng  LIU Xiao-hui  WANG Meng-yong  HAO Wen-jing
Affiliation:1. Yantai Electric Power Design Institute, Yantai 264002, China; 2. Shandong Electric Power Corporation, Jinan 250001, China; 3. Lunan Geologieal Exploration Institute, Yanzhou 272100, China
Abstract:Current electric models of phase-change towers used in 500 kV double-circuit transmission line have disadvantages,such as ice-induced composite insulator skirt short circuit and weak lightning protection.By installation of side-rod to improve the jumper lightning-proof,changing the jumper exit angle to improve insulator high voltage side field distribution,using U-shaped guyed suspension insulator string and strained insulator string of internal arc structure to avoid the core twisting with terminal hardware,changing the jumper to V shape to prevent dust,rain and icing flashovers,using composite insulators in strained insulator string to make the double-circuit phase-change towers free of cleaning,the electric model can be optimized.
Keywords:500 kV double-circuit transmission line  transposition tower  electric model  design optimization