首页 | 本学科首页   官方微博 | 高级检索  
     

小型HFC-32冷水(热泵)机组的性能试验研究
作者单位:;1.环境保护部环境保护对外合作中心;2.浙江盾安人工环境股份有限公司
摘    要:开发了小型HFC-32风冷冷水(热泵)机组和水(地)源热泵机组,针对风冷机组开展了名义制冷工况、名义制热工况、制冷最大负荷以及制热最大负荷等工况的系列试验,针对水(地)源热泵机组开展了水环式、地下水式以及地埋管式应用场合的名义制冷和名义制热试验,试验结果表明,与同规格的HFC-410A机组相比,HFC-32机组的制冷(热)量、功率均有所提升,能效略低一些,压缩机排气温度上升16.5~19.5℃。

关 键 词:HFC-32  风冷冷水(热泵)机组  水(地)源热泵机组  性能试验

Performance Test for Small HFC-32 Water Chilling( Heat Pump) Unit
Affiliation:,Foreign Economic Cooperation Office,Ministry of Environmental Protection of China,Zhejiang Dun'an Artificial Environment Co.,Ltd.
Abstract:Small HFC-32 air-cooled water chilling( heat pump) unit and water( ground) source heat pump unit is developed. The performance of air-cooled water chilling( heat pump) unit under series conditions are tested,including nominal cooling condition,nominal heating condition,maximum cooling load condition and maximum heating load condition. The performance of water(ground)source heat pump unit for water-loop application,ground-water application and ground-loop application under series conditions are also tested,including nominal cooling condition and nominal heating condition. The conclusions indicate that compared with similar HFC-410 A unit,the cooling( heating) capacity and power consumption of HFC-32 unit are higher than HFC-410 A unit,the energy efficiency for HFC-32 unit is a little lower than HFC-410 A unit,and the compressor exhaust temperature of HFC-32 unit is 16. 5 ~ 19. 5℃ higher than HFC-410 A unit.
Keywords:HFC-32  air-cooled water chilling(heat pump) unit  water(ground) source heat pump unit  performance test