Extinguishment of compartment fires using portable chemical extinguishers and water |
| |
Authors: | M.A. Kokkala |
| |
Affiliation: | Technical Research Centre of Finland, Fire Technology Laboratory, 02150, Espoo 15, Finland |
| |
Abstract: | ![]() Extinguishing experiments on post-flashover room fires, using various kinds of portable extinguihers or water jets, are reported. Typically 2–3 kg of AB-type (general purpose) powders were required to put out test fires of almost 5 MW heat release rate. With water the minimum flow for extinction was 17 l/min or 7.5 g/m2 s. When halon or B-type powder was used the fire re-ignited. |
| |
Keywords: | |
本文献已被 ScienceDirect 等数据库收录! |
|