首页 | 本学科首页   官方微博 | 高级检索  
     


Measurements of household electricity and domestic hot water use in dwellings and the effect of different monitoring time resolution
Authors:Hans Bagge  Dennis Johansson  
Affiliation:a Building Physics, Lund University, Lund, Sweden;b Swegon AB, Tomelilla, Sweden
Abstract:The use of household electricity and domestic hot water has been measured for 72 apartments in an apartment building located in the south of Sweden. The measurements were carried out with samples every 6 s, a tenfold increase in resolution compared to available published data, during a measurement period of five days, in the winter season, including a weekend. The influence of the time resolution on the distribution of data was analysed by integrating the 6 s data to represent longer logging intervals. Extreme values, especially the high values, are shown to be reduced if the time interval is increased. The maximum household electric power was 50% higher at a 6 s resolution compared to 60 s and the corresponding difference for domestic hot water flow was 40%. Daily variations has to be considered for photovoltaic installations and solar thermal collectors, energy simulations of buildings need at least hourly data and all kind of power design in a building or its services benefits from much more resolved data.
Keywords:Household electricity   Domestic hot water   Energy use   Monitoring
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏