A combined-cycle refrigeration system using ejector-cooling cycle as the bottom cycle |
| |
Authors: | B. J. Huang V. A. Petrenko J. M. Chang C. P. Lin S. S. Hu |
| |
Affiliation: | Department of Mechanical Engineering, National Taiwan University, Taipei, Taiwan |
| |
Abstract: | A combined-cycle refrigeration system (CCRS) that comprises a conventional refrigeration and air-conditioning system using mechanical compressor (RAC/MC) and an ejector-cooling cycle (EJC) is proposed and studied. The EJC is driven by the waste heat from the RAC/MC and acts as the bottom cycle of the RAC/MC. A system analysis shows that the COP of a CCRS is significantly higher than a single-stage refrigeration system. Improvement in COP can be as high as 18.4% for evaporating temperature of the RAC/MC Te at −5°C. A prototype of the CCRS was built and tested in the present study. Experimental results show that at Te=−4.5°C, COP is improved by 14% for a CCRS. For Te at 5°C, COP can be improved by 24% for a CCRS with higher condensing temperature of the RAC/MC. The present study shows that the CCRS using the ejector-cooling cycle as the bottom cycle of the RAC/MC is viable. Further improvement in COP is possible since the prototype is not designed and operated at an optimal condition. |
| |
Keywords: | Refrigerating system Compression system Ejection system Combined system Subcooling Design PerformanceSystè me frigorifique Systè me à compression Systè me à é jection Systè me mixte Sous-refroidissement Conception Performance |