反渗透前不锈钢换热器失效的原因及其防护
引用本文:刘春红,许好好.反渗透前不锈钢换热器失效的原因及其防护[J].腐蚀与防护,2006,27(4):212-214.
作者姓名:刘春红  许好好
作者单位:浙江省嘉兴发电有限责任公司,嘉兴,314201
摘    要:嘉兴发电厂二期工程化学补给水系统两套板框式316不锈钢加热器在短时间内相继损坏失效,在对换热器运行条件、失效宏观特征、腐蚀产物特征和材料化学成分的分析后,得出了应力腐蚀破裂的结论,并提出了相应的防范措施。

关 键 词:不锈钢  换热器  氯离子  应力腐蚀破裂
文章编号:1005-748X(2006)04-0212-03
收稿时间:2005-07-04
修稿时间:2005-08-15

FAILURE ANALYSIS OF STAINLESS STEEL HEAT EXCHANGERS IN A REVERSE OSMOSIS SYSTEM
LIU Chun-hong,XU Hao-hao.FAILURE ANALYSIS OF STAINLESS STEEL HEAT EXCHANGERS IN A REVERSE OSMOSIS SYSTEM[J].Corrosion & Protection,2006,27(4):212-214.
Authors:LIU Chun-hong  XU Hao-hao
Affiliation:Jiaxing Power Generation Co, , Ltd. , Jiaxing 314201, China
Abstract:After a short period of service,two 316 stainless steel heat exchangers of the chemical feedwater system in a power plant were corroded.Through analyzing the operating conditions,crack characters,corrosion products and chemical composition of the material,it was concluded that the failure was caused by stress corrosion cracking(SCC).Some prevention measures were presented.
Keywords:Stainless steel  Heat exchanger  Chlorion  Stress corrosion cracking