高肇直流融冰运行模式下无功功率和谐波特性分析
引用本文:谢惠藩,王海军,陈潜.高肇直流融冰运行模式下无功功率和谐波特性分析[J].电力系统自动化,2011,35(19):77-84.
作者姓名:谢惠藩  王海军  陈潜
作者单位:中国南方电网超高压输电公司检修试验中心,广东省广州市,510663
基金项目:中国南方电网科技基金项目
摘    要:为研究高肇(高坡一肇庆)直流融冰模式、正常模式的无功特性和谐波特性,基于EMTDC搭建了±500kV高肇直流背靠背融冰详细模型并重点针对融冰模式、正常模式下换流站的无功特性和交直流侧谐波特性进行仿真研究。仿真结果表明:高坡站融冰模式的无功消耗比正常模式略大,肇庆站融冰模式的无功消耗则比正常模式略小;融冰模式下换流站交流谐波电流幅值比正常模式小、畸变率比正常模式大,而交流谐波电压及其畸变率均比正常模式小;融冰模式下同一换流站中两极处于不同的运行状态,两极直流侧谐波特性不相同。该研究结果为高肇直流在融冰方式下滤波器的投切提供一定的理论指导。

关 键 词:直流融冰功能  电磁暂态仿真  双极功率异向传输  无功功率  谐波分析  特征谐波  非特征谐波
收稿时间:12/8/2010 2:17:16 AM
修稿时间:9/19/2011 4:32:25 PM

Analysis on Reactive Power and Harmonics of Gao-Zhao HVDC Under Deicing Operation Mode
XIE Huifan,WANG Haijun,CHEN Qian.Analysis on Reactive Power and Harmonics of Gao-Zhao HVDC Under Deicing Operation Mode[J].Automation of Electric Power Systems,2011,35(19):77-84.
Authors:XIE Huifan  WANG Haijun  CHEN Qian
Affiliation:XIE Huifan,WANG Haijun,CHEN Qian (China Southern Power Grid EHV Maintenance & Test Center,Guangzhou 510663,China)
Abstract:To study the characteristics of reactive power and harmonic of Gao-Zhao high voltage direct current(HVDC) under deicing operation mode and normal operation mode,an EMTDC model of ±500 kV Gao-Zhao HVDC with direct current power forth-and-reverse transmission deicing function is introduced in detail.With this model the characteristics of reactive power and harmonic at converter station are analyzed.Simulations show that:(1) Reactive power consumption at Gaopo converter station under deicing operation mode is larger than that under normal operation mode,while Zhaoqing converter station is on the contrary;(2) The amplitude of harmonic alternative current is smaller and total harmonic current distortion rate is larger compared to the normal operation mode,and the amplitude and harmonic distortion rate of alternative current voltage are both smaller than that of normal operation mode;(3) The two poles operating at different modes and the harmonic in direct system of each pole in the same converter station is different.Simulation results are helpful to the control of alternative current filter control under deicing operation mode.
Keywords:direct current power deicing function  EMTDC  direct current power forth-and-reverse transmission  reactive power  harmonic analysis  characteristic harmonic  non-characteristic harmonic