Dielectric breakdown of a residual SF6 plasma at 3000 Kunder diatomic equilibrium |
| |
Authors: | Yan J.D. Fang M.T.C. Liu Q.S. |
| |
Affiliation: | Dept. of Electr. Eng. & Electron., Liverpool Univ.; |
| |
Abstract: | A residual plasma at 3000 K and under diatomic equilibrium is left inside an axially blown gas blast SF6 circuit breaker after the thermal extinction of an arc. The breakdown of such a residual plasma depends on the electron generation and loss mechanisms. Altogether six ionization and chemical reactions relevant to the time scale of breakdown have been taken into account. It has been found that the critical field strength for breakdown is proportional to the pressure and is equal to 2.0 V/(m.Pa). This field strength is in agreement with the experimental results |
| |