首页 | 本学科首页   官方微博 | 高级检索  
     


Influence of inclination angle,attack angle,and arrangement of rectangular vortex generators on heat transfer performance
Authors:Takeo Tanaka  Masaaki Itoh  Toshio Hatada  Hitoshi Matsushima
Abstract:We have studied the enhancement of heat transfer by vortex generators. Experiments were performed on rectangular‐type vortex generators mounted on a parallel‐plate heater, and the heat transfer coefficient of the heater surface and pressure drop in the duct were measured. These measurements indicated that a rectangular vortex generator (called a double‐inclined winglet), with inclination angle of the vortex generator surface to the heater surface (β) at 60°, and the attack angle to the flow direction (γ) at 45°, maximizes the local Nusselt number of the heater surface. It was also found that a group of double‐inclined winglets has an optimal arrangement in a winglet array, longitudinal pitch and transverse pitch, that maximizes the ratio Colburn's dimensionless heat transfer coefficient JH]/friction factor f]. The results of numerical calculations showed that the double‐inclined winglet was superior to the conventional rectangular vortex generator in heat transfer. © 2003 Wiley Periodicals, Inc. Heat Trans Asian Res, 32(3): 253–267, 2003; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/htj.10089
Keywords:heat transfer enhancement  heat exchanger  vortex generator  separation  flow control
设为首页 | 免责声明 | 关于勤云 | 加入收藏