用超高频局部放电测量法实现电力变压器局部放电的在线监测
引用本文:黄兴泉,赵善俊,宋志国,黄中华,张欲晓,李成榕. 用超高频局部放电测量法实现电力变压器局部放电的在线监测[J]. 中国电力, 2004, 37(8): 52-56
作者姓名:黄兴泉  赵善俊  宋志国  黄中华  张欲晓  李成榕
作者单位:1. 河南电力试验研究所,河南,郑州,450052
2. 濮阳供电公司,河南,濮阳,475003
3. 开封市电业局,河南,开封,457000
4. 华北电力大学,北京,100085
摘    要:高频局部放电测量法(UHF法)与传统的脉冲电流法完全不同,它采集的被测信号为局部放电过程所产生的超高频电磁波:利用UHF法可有效解决电力变压器局部放电在线监测中的抗干扰问题。文中结合变压器结构设计的放油阀式和人孔/手孔盖式超高频信号传感器安装在220kV和110kV电压等级变压器上,成功地捕捉到变压器内部局部放电产生的超高频信号。对变压器局部放电故障诊断的判据等问题进行讨论,为变压器超高频局部放电在线监测方法的应用积累了经验。

关 键 词:超高频 局部放电 在线 电力变压器
文章编号:1004-9649(2004)08-0052-05
修稿时间:2004-02-23

Partial discharge detection on-line in transformer using UHF
HUANG Xing-quan,ZHAO Shan-jun,SONG Zhi-guo,HUANG Zhong-hua,ZHANG Yu-xiao,LI Cheng-rong Henan Electric Power Research Institute,Zhengzhou ,China, Puyang Power Supply Company,Puyang ,China, Kaifeng Power Supply Company,Kaifeng ,China, North China Electric Power University,Beijing ,China. Partial discharge detection on-line in transformer using UHF[J]. Electric Power, 2004, 37(8): 52-56
Authors:HUANG Xing-quan  ZHAO Shan-jun  SONG Zhi-guo  HUANG Zhong-hua  ZHANG Yu-xiao  LI Cheng-rong Henan Electric Power Research Institute  Zhengzhou   China   Puyang Power Supply Company  Puyang   China   Kaifeng Power Supply Company  Kaifeng   China   North China Electric Power University  Beijing   China
Affiliation:HUANG Xing-quan,ZHAO Shan-jun,SONG Zhi-guo,HUANG Zhong-hua,ZHANG Yu-xiao,LI Cheng-rong Henan Electric Power Research Institute,Zhengzhou 450052,China, Puyang Power Supply Company,Puyang 475003,China, Kaifeng Power Supply Company,Kaifeng 457000,China, North China Electric Power University,Beijing 100085,China
Abstract:The partial discharge measurement with ultrahigh frequency (UHF) is completely different from conventional impulse-currentmeasurement, which collects the measured signal of ultrahigh frequency electromagnetic wave produced in the course of partial discharge.To use UHF can efficiently solve the problem of anti--interference in online monitoring of power transformer partial discharge. The paperintroduces that the ultrahigh frequency signal produced by partial discharge in internal transformer can be found successfully, combinedwith the transformer structural design that the ultrahigh frequency signal sensors with the types of oil drain valve and manhole/hand holecover are installed in 220 kV and 110 kV transformers. The paper discusses the problems such as criterion for the fault diagnosis of transformerpartial discharge, Which accumulates the experiences for the application of online monitoring method of ultrahigh frequency partial dischargeof transformer.
Keywords:ultrahigh frequency  partial discharge  on-line  power transformer