10 kV系统冲击与工频续流联合试验回路设计
引用本文:陈斯翔,苏杏志,孔华东,孙广慧,刘益军,齐小军.10 kV系统冲击与工频续流联合试验回路设计[J].电力建设,2015,36(8):102-107.
作者姓名:陈斯翔  苏杏志  孔华东  孙广慧  刘益军  齐小军
作者单位:1. 广东电网有限责任公司佛山供电局,广东省佛山市528000;2. 武汉水院电气有限责任公司,武汉市 430073
基金项目:南方电网公司科技项目(K-GD2013-0268)。
摘    要:为检验10 kV带间隙防雷装置在冲击闪络后熄灭工频续流电弧的能力,设计了一种冲击试验与工频续流试验相结合的试验回路。为了产生较高电压下的高幅值工频续流,采用LC串并联谐振回路产生工频续流,对该回路中各元件的参数进行计算并给出合理数值,最后利用同步控制回路提取冲击信号来导通工频续流回路,实现冲击试验与工频续流试验的同步。计算结果表明,该联合试验回路能在产生1.2/50 μs冲击波的同时产生频率为50 Hz的正弦电流波且电流的振荡能够持续至少100 ms,满足带间隙防雷装置在冲击闪络后,检验工频续流下熄灭电弧能力的要求。

关 键 词:带间隙防雷装置  LC串并联谐振  工频续流  联合试验  同步控制  

10 kV Combined Test Circuit Design with Impulse and Power Frequency Continuous Current
CHEN Sixiang,SU Xingzhi,KONG Huadong,SUN Guanghui,LIU Yijun,QI Xiaojun.10 kV Combined Test Circuit Design with Impulse and Power Frequency Continuous Current[J].Electric Power Construction,2015,36(8):102-107.
Authors:CHEN Sixiang  SU Xingzhi  KONG Huadong  SUN Guanghui  LIU Yijun  QI Xiaojun
Affiliation:1. Foshan Power Supply Bureau of Guangdong Power Grid Co., Ltd., Foshan 528000, Guangdong Province, China; 2. Wuhan Shuiyuan Electrical Co., Ltd., Wuhan 430073,  China
Abstract:To test the capability of 10 kV lightning protection device with series gaps to cut off the power frequency continuous current after the device breakdown by lightning, this paper designed a test loop in combination with impulse test and power frequency continuous current test. In order to generate power frequency continuous current with high amplitude under higher voltage, a LC series and parallel resonant circuit was used in which the parameters of each element were calculated and selected and their reasonable values were given. Finally, a synchronization control circuit was chosen to extract the impulse signal to conduct the power frequency continuous current circuit, which could realize the synchronization in impulse test and power frequency continuous current test. The calculation results show that the combined test circuit can generate 1.2/50 μs impulse waveform, and 50 Hz sinusoidal current wave with 100 ms oscillation, which can meet the requirement of testing the capability of lightning protection device with series gaps to cut off electric arc under power frequency continuous current after the device breakdown by lightning.
Keywords:lightning protection device with series gaps  LC series and parallel resonant  power frequency continuous current  combined test  synchronization control  