Characteristics of cooling water fouling in a heat exchange system |
| |
Authors: | Sun-Kyung Sung Sang-Ho Suh Dong-Woo Kim |
| |
Affiliation: | (1) Dept. of Building Equipment System Engineering, Kyungwon University, Sungnam Kyonggi, 461-702, Korea;(2) Dept. of Mechanical Engineering, Soongsil University, Seoul, 156-743, Korea;(3) Dept. of Building Technology, Suwon Science College, Hwasung, Kyonggi, 445-742, Korea |
| |
Abstract: | This study investigated the efficiency of the physical water treatment method in preventing and controlling fouling accumulation on heat transfer surfaces in a laboratory heat exchange system with tap and artificial water. To investigate the fouling characteristics, an experimental test facility with a plate type heat exchange system was newly built, where cooling and hot water moved in opposite directions forming a counter-flow heat exchanger. The obtained fouling resistances were used to analyze the effects of the physical water treatment on fouling mitigation. Furthermore, the surface tension and pH values of water were also measured. This study compared the fouling characteristics of cooling water in the heat exchange system with and without the mitigation methods for various inlet velocities. In the presence of the electrode devices with a velocity of 0.5m/s, the fouling resistance was reduced by 79% compared to that in the absence of electrode devices. |
| |
Keywords: | Fouling Fouling factor Precipitation fouling Physical water treatment Heat exchange system Anti-fouling technology |
本文献已被 SpringerLink 等数据库收录! |
|