TEV与HFCT法测量开关柜局部放电的特性对比
引用本文:谢荣斌,杨超,申强,李诗勇,罗勇,于泊宁.TEV与HFCT法测量开关柜局部放电的特性对比[J].中国电力,2022,55(3):37-47.
作者姓名:谢荣斌  杨超  申强  李诗勇  罗勇  于泊宁
作者单位:1. 贵州电网有限责任公司贵阳供电局, 贵州 贵阳 550004;2. 西安交通大学 电气工程学院, 陕西 西安 710049
基金项目:中国南方电网有限责任公司科技项目(面向智能配电网的分布式状态感知应用技术研究,GZKJXM20190127)。
摘    要:探究了暂态对地电压(transient earth voltage,TEV)法对于开关柜局部放电现象的检测性能,并与脉冲电流检测的效果进行了对比.研究了二者对于不同类型局部放电的检出能力;分析了2种方法测量下4种局部放电PRPD(phase resolved partial discharge)图谱的相似性与差异;通过...

关 键 词:局部放电  暂态对地电压  脉冲电流检测  PRPD图谱  统计特征
收稿时间:2021-08-26
修稿时间:2021-09-21

Comparative Study on the Switchgear Partial Discharge Characteristics Based on Transient Earth Voltage and Pulse Current Detection Methods
XIE Rongbin,YANG Chao,SHEN Qiang,LI Shiyong,LUO Yong,YU Boning.Comparative Study on the Switchgear Partial Discharge Characteristics Based on Transient Earth Voltage and Pulse Current Detection Methods[J].Electric Power,2022,55(3):37-47.
Authors:XIE Rongbin  YANG Chao  SHEN Qiang  LI Shiyong  LUO Yong  YU Boning
Affiliation:1. Guiyang Power Supply Bureau of Guizhou Power Grid Co., Ltd., Guiyang 550004, China;2. School of Electrical Engineering, Xi'an Jiaotong University, Xi'an 710049, China
Abstract:The transient earth voltage (TEV) method is studied in detection performance for switchgear partial discharge, and compared with the pulse current detection method. In addition, the detection capabilities of the two methods are studied for different types of partial discharge, and the similarities and differences of the PRPD (phase resolved partial discharge) spectra of four partial discharge types measured by two methods are analyzed. The variations of the detection results with the applied voltage are analyzed through calculating the statistical characteristics. The results show that, compared with the conventional high-frequency current transformer (HFCT) method, the TEV method has a lower signal-noise ratio in detecting switchgear partial discharge with a slightly inferior detection performance, but it is more suitable for detecting weak tip discharge; in terms of PRPD spectra, the two methods have strong consistency in pulse amplitude characteristics and phase intervals for different types of partial discharge, but there are some differences in pulse concentration and other aspects. With the change of applied voltage, TEV and HFCT methods have the same variation trend of skewness and steepness, and both methods can effectively reflect the discharge characteristics of partial discharge.
Keywords:partial discharge  transient earth voltage  current pulse detection  PRPD spectrum  statistical characteristics  