Experimental study of turbulent single-phase flow and heat transfer inside a micro-finned tube |
| |
Authors: | Mansoor Siddique Majed Alhazmy |
| |
Affiliation: | aDepartment of Thermal Engineering and Desalination Technology, King Abdul Aziz University, P.O. Box 80204, Jeddah 21589, Saudi Arabia |
| |
Abstract: | Single-phase heat transfer and pressure drop characteristics of a commercially available internally micro-finned tube with a nominal outside diameter of 7.94 mm were studied. Experiments were conducted in a double pipe heat exchanger with water as the cooling as well as the heating fluid for six sets of runs. The pressure drop data were collected under isothermal conditions. Data were taken for turbulent flow with 3300 ≤ Re ≤ 22,500 and 2.9 ≤ Pr ≤ 4.7. The heat transfer data were correlated by a Dittus–Boelter type correlation, while the pressure drop data were correlated by a Blasius type correlation. The correlation predicted values for both the Nusselt number and the friction factors were compared with other studies. It was found that the Nusselt numbers obtained from the present correlation fall in the middle region between the Copetti et al. and the Gnielinski smooth tube correlation predicted Nusselt number values. For pressure drop results, the present correlation predicted friction factors values were nearly double that of the Blasius smooth tube correlation predicted friction factors. It was also found that the rough tube Gnielinski and Haaland correlations can be used as a good approximation to predict the finned tube Nusselt number and ffriction factor, respectively, in the tested Reynolds number range. |
| |
Keywords: | Heat exchanger Experiment Heat transfer Pressure drop Micro-finned tube CorrelationMots clé s: É changeur de chaleur Expé rimentation Transfert de chaleur Chute de pression Tube micro-aileté Corré lation |
本文献已被 ScienceDirect 等数据库收录! |