首页 | 本学科首页   官方微博 | 高级检索  
     

OPGW光纤复合架空地线异常发热现场测量分析及仿真
引用本文:彭向阳,刘毅刚,张穗强.OPGW光纤复合架空地线异常发热现场测量分析及仿真[J].电网技术,2012,36(2):206-211.
作者姓名:彭向阳  刘毅刚  张穗强
作者单位:1. 广东电力科学研究院,广东省广州市,510600
2. 广州供电局,广东省广州市,510600
摘    要:针对光纤复合架空地线(optical fiber compositeoverhead ground wire,OPGW)在变电站构架连接处的异常发热问题,对其接地回路感应电流、电压进行现场实测,分析出异常发热原因是构架处OPGW主接地不良导致接地电流转移至耐张连接回路,且发热功率较大及较集中。据此进一步开展OPGW感应电流、发热功率的仿真研究,仿真与实测数据基本吻合。研究表明线路负荷电流、杆塔接地电阻以及OPGW与构架连接接触电阻对OPGW接地回路分流及发热功率存在不同程度的影响。

关 键 词:光纤复合架空地线  异常发热  感应电流  发热功率  现场测量  电磁仿真

On-site Measurement Based Analysis and Simulation of Abnormal Heating of Optical Fiber Composite Overhead Ground Wires
PENG Xiangyang,LIU Yigang,ZHANG Suiqiang.On-site Measurement Based Analysis and Simulation of Abnormal Heating of Optical Fiber Composite Overhead Ground Wires[J].Power System Technology,2012,36(2):206-211.
Authors:PENG Xiangyang  LIU Yigang  ZHANG Suiqiang
Affiliation:1.Guangdong Electric Power Research Institute,Guangzhou 510600,Guangdong Province,China;2.Guangzhou Power Supply Bureau,Guangzhou 510600,Guangdong Province,China)
Abstract:In allusion to the phenomenon of abnormal heating at the joint where the optical fiber composite overhead ground wire(OPGW) is connected to the truss of substation,the on-site measurement of the induced current and voltage of the grounding circuit of OPGW was performed,and based on the measured results the reason causing the abnormal heating was analyzed.Analysis results showed that the bad contact of OPGW with the truss made the grounding current of OPGW transferring to the circuit of tensional joint and the heating power was larger and concentrated.On this basis the simulation research on induced current of OPGW and heating power are conducted,and simulation results basically conform to the measured data.Research results show that power flow of transmission line,tower grounding resistance and contact resistance of the joint where OPGW is connected to the truss differently influence on the shunt of grounding current of OPGW and the heating power.
Keywords:optical fiber composite overhead ground wire (OPGW)  abnormal heating  induced current  heating power  on-site measurement  electromagnetic simulation
本文献已被 CNKI 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号