首页 | 本学科首页   官方微博 | 高级检索  
     


Experimental setup for precise measurement of losses in high-temperature superconducting transformer
Authors:Z. Janu  P. Repa  F. Zizek  F. Soukup
Affiliation:a Institute of Physics of the Academy of Sciences of the Czech Republic, Na Slovance 2, 182 21 Prague 8, Czech Republic
b Charles University, Faculty of Mathematics and Physics, V Holesovickach 2, 180 00 Prague 8, Czech Republic
c Skoda Research Ltd., Tylova 57, 316 00 Plzen, Czech Republic
Abstract:
A simple cryogenic system for testing of the superconducting power transformer was constructed. Thermal shielding is provided by additional liquid nitrogen bath instead of super-insulation. The system, together with use of a precise nitrogen liquid level meter, permitted calorimetric measurements of losses of the 8 kVA HTS transformer with a resolution of the order of 0.1 W.
Keywords:Superconducting transformer   AC losses   Calorimeters